THE INSTALLER MUST ENSURE:
• THE SEAL AROUND THE RECESSING HOUSING IS WATERPROOF TO PREVENT ANY INGRESS
OF WATER;
• ANY WATER ACCIDENTALLY ENTERING THE RECESSING HOUSING (E.G. CONDENSATION, RUN
OFF, LEAKS, ETC.) HAS AN EXTERNAL DRAINAGE POINT TO PREVENT ANY STAGNATION;
• THE INTEGRITY OF THE SEALS BETWEEN THE STAINLESS STEEL WALL PLATE AND THE WALL
OR THE WALL PLATE AND THE VALVE AT LEAST ONCE A YEAR, AND MAKE GOOD IF NECESSARY.
If this advice is not followed, water may leak into the wall.
DELABIE cannot be held responsible for any ingress.
FOR FURTHER INFORMATION PLEASE CALL DELABIE TECHNICAL SUPPORT
UK: 01491 821821. ALL OTHER MARKETS: +33 (0)3 22 60 22 74.
REMEMBER
• Our taps must be installed by professional installers in accordance with current regulations and
recommendations in your country, and the specifications of the fluid engineer.
• Sizing the pipes correctly will avoid problems of flow rate, pressure loss and water hammer (see
calculation table in our brochure and online at www.delabie.com).
• Protect the installation with filters, water hammer absorbers and pressure reducers to reduce the
frequency of maintenance (recommended pressure from 1 to 5 bar maximum).
• Install stopcocks close to the tap to facilitate maintenance.
• The pipework, filters, non-return valves, stopcocks, bib taps, cartridge and all sanitary fittings should
be checked at least once a year, and more frequently if necessary.
HOW TO OPERATE THE ELECTRONIC UNIT (Fig. A, B, C, D or E)
• When the power supply is operating the yellow LED "IN-12V" i (Fig. E) is lit on the Primary Circuit
Board (PCB).
Voluntary flush:
• The flush is activated when the hand is detected ~4cm in front of the sensor j (Fig. A, B, C or D).
The green LED for the solenoid valve k (Fig. E) lights up on the electronic unit and the red LED
is lit on the sensor j.
• Successive flushes are possible.
• Voluntary flush has priority and cancels the automatic function.
Automatic flush:
• The user is detected after 8 seconds in the detection range j.
• The red LED j on the sensor flashes.
• Rinsing occurs 5 seconds after the user leaves the sensor detection range. The green LED for
the solenoid valve k (Fig. E) lights up on the electronic unit and the red LED is lit on the sensor j.
ADJUSTMENT (Fig. E)
Detection distance:
• Can be adjusted from 50-90cm via the potentiometer "GAIN" l in the electronic unit.
We do not recommend using the minimum or maximum positions.
• The detection distance is pre-set at the factory to approx. 70cm.
• To change the detection range:
- Switch to position "R" on the electronic unit m to adjust.
- Turn the potentiometer "GAIN" l to the minimum position before adjusting to the required detection
distance.