PROGRAMMING
The following (Table 5) lists all available commands and parameters for the Pentair Pentek Intellidrive ® Constant Pressure Pump
Controller .
Menu
Parameter
Settings
Hour Format
Time/Date
Time
Date
Proportional Gain
Integration Time
PID Control
Derivation Time
Derivative Limit
Boost
Differential
Boost Delay
Sleep
Wake Up
Differential
Wake Delay
Password Time
Out
Password
Password
Internal
Setpoints
Setpoints
External
Setpoints
Sub Menu
Parameter
Motor Phase
Connection Type
Motor Type
Motor
Service Factor
Amps
Min Frequency
Max Frequency
Max Sensor
Sensor
Value
PN957 (25-06-20)
Value
Unit of Measure
Default
Min.
Hours
12Hr
12Hr
HH:MM
1:00 AM
1
MM/DD/YYYY
1/1/12
–
–
1500
0
Milliseconds
1500 ms
20 ms
Milliseconds
60 ms
0 ms
–
120
0
PSI
3 PSI
3 PSI
MM:SS
1 Min
30 Sec
PSI
5 PSI
5 PSI
MM:SS
15 Sec
3 Sec
HH:MM
1 Hr
1 Min
–
7777
0000
PSI
60 PSI
15 PSI
PSI
40 PSI
15 PSI
Unit of Measure
Default
Min
_
1
1
–
3 wire
3 wire
–
Subm
Subm
A
00.0 A
00.0 A
Hz
30 Hz
30 Hz
1 above
Hz
60 Hz
Min Hz
PSI
100 PSI
100 PSI
Table 5 - Main Menu and Parameters
Max.
24Hr
Selects 12 or 24 hour time scale.
24
Sets current time. Used for time stamp in fault log.
–
Sets current date. Used for date stamp in fault log.
Sets the PID controller gain. Used in conjunction with all PID Control
10000
parameters to control how fast or slow the Intellidrive reacts to pressure
changes.
Sets the PID controller integration time. Used in conjunction with all
65000 ms
PID Control parameters to control how fast or slow Intellidrive reacts to
pressure changes.
Sets PID controller derivation time. Used in conjunction with all PID
10000 ms
Control parameters to control how fast or slow Intellidrive reacts to
pressure changes.
2000
Sets derivative filter time constant for PID controller.
First part of Boost Process. Pressure boost that happens before it goes
10 PSI
to Wake Delay.
The time Intellidrive takes to start Boost Process after system has
5 Min
stabilized.
15 PSI
Pressure amount below setpoint that wakes up Intellidrive.
Second part of the Boost Process. The time it takes to ramp down
2 Min
pressure during the Boost Process.
6 Hr
Amount of time it takes to lock keypad (after last button is pressed).
9999
Password used to unlock keypad.
Max Sensor
Main pressure setpoint used. Sets main system operational pressure.
Value minus
This parameter is accessed here, through PSI Preset button, or by
3 PSI
pressing Enter button while in Constant Pressure operation.
Second pressure setpoint. When another pressure setting is desired
Max Sensor
other than Internal Setpoint. Additional programming needed in I/O
Value minus
section. Requires an external switch or timer to be wired to digital input
3 PSI
terminals. It is only active when there is voltage present at the digital
input terminals.
Max
Selects phase of motor to be operated. An additional sub menu will
3
appear, based on phase selection, to select proper motor type.
Wire type for 1 phase motor operation only. Can only access by first
2 wire
setting Motor Phase parameter to 1 Phase.
Motor type for 3 phase motor operation only. Can only access by first
Above Gnd
setting Motor Phase parameter to 3 Phase.
Per
Service factor amps (max. load) of motor the Intellidrive is operating. Sets
Intellidrive
maximum allowed amps at output of Intellidrive. See Table 8 for values.
and motor
1 below Max
Minimum frequency (speed) motor will run.
Hz
Maximum frequency (speed) motor will run. Up to 80Hz is only available on
80 Hz
submersible 3-phase motors (when motor is 2x the HP of pump).
Maximum pressure value of transducer sensor used with Intellidrive. Only
300 PSI
change if different transducer is used with Intellidrive, other than 100 PSI
max scale.
Description
Description
13