INITIAL SETUP
INITIAL STARTUP
Ensure that the cover is installed before operating the Pentair
Pentek Intellidrive ® Constant Pressure Pump Controller.
Most installations will only require the initial startup settings.
However, the installer may need to set additional parameters.
Information about accessing all parameters, explanations of their
functions, and procedures for changing parameter values, will be
found later in this section.
Motor Type
Part Number
P42B0005A2-01
P42B0007A2-01
P42B0010A2-01
P42B0015A2-01
P42B0005A2-02
P42B0007A2-02
2-Wire
P42B0010A2-02
P42B0015A2-02
P42B0005A2
P42B0007A2
P42B0010A2
P42B0015A2
P43B0005A2-01
P43B0007A2-01
P43B0010A2-01
P43B0015A2-01
P43B0005A2-02
P43B0007A2-02
CS/CR 3-Wire
P43B0010A2-02
P43B0015A2-02
P43B0005A2
P43B0007A2
P43B0010A2
P43B0015A2
P43B0020A2
P43B0005A3
P43B0007A3
P43B0010A3
3-Phase
P43B0015A3
P43B0020A3
P43B0030A3
P43B0050A3
Table 2 - Pentek Motor Service Factor Amps
1.
Program the Intellidrive: Apply power to the device. Setup
Guide will appear in the display. Follow keypress sequence
shown in Figure 10.
If Setup Guide does not appear, refer to Intellidrive Reset
NOTE:
Procedure (Figure 20).
10
Rating @ 230V
Service Factor
Amps
HP
1/2
4.7
3/4
6.2
1
8.1
1-1/2
10.4
1/2
5.1
3/4
6.1
1
8.0
1 1/2
10.6
1/2
4.7
3/4
6.4
1
9.1
1-1/2
11.0
1/2
4.8
3/4
6.0
1
7.3
1-1/2
10.9
1/2
4.5
3/4
5.7
1
6.8
1 1/2
10.7
1/2
4.9
3/4
6.3
1
7.2
1-1/2
11.1
2
12.2
1/2
2.9
3/4
3.9
1
4.7
1-1/2
6.1
2
7.6
3
10.1
5
17.5
1 Phase
Connection Type
(2 Wire or 3 Wire)
Enter Service Factor Amps
Figure 10 - Intellidrive Setup Guide
2.
Select 80 Hz Operation, if necessary (See 60 Hz to 80 Hz
Operation for more information):
Press MAIN MENU button.
Follow the keypress sequence shown in Figure 11.
Press MAIN MENU button
Use arrows to select
Press Enter to save
Figure 11 - Select 80 Hz
(3-phase submersible operation only)
3.
Pump out well, if necessary. Direct discharge to appropriate
location not connected to system and press Pump Out.
The pump will run at 45 Hz. Adjust frequency as appropriate:
Press ENTER
Change frequency value. Above ground pumps should run at
60 Hz for this step (until pump is primed). Then adjust frequency
as necessary.
Press ENTER again.
Apply 230V to Drive
Enter Motor Phase
(1 Phase or 3 Phase)
Press Enter
3 Phase
Motor Type
Subm or Above Gnd
Press Enter
Press Enter
Set Time
Press Enter
Set Date
Press Enter
Setup Complete
Use arrows to
scroll to Motor
Press Enter
Max Frequency
Press Enter
Use arrows to
select 80 Hz
6570 0512_EN
PN957 (25-06-20)
6566 0512