Bosch Praesideo 4.3 Manual De Uso página 59

Sistema de megafonía y sistema acústico de emergencia
Tabla de contenido
Praesideo 4.3
Clause / Requirement
8.6.2 The audible indication shall be silenced automatically
if the VACIE is automatically reset from the fault warning
condition.
8.6.3 If previously silenced, the audible indication shall
resound for each newly recognized fault.
8.7 Reset of fault indications
8.7. 1 Indications of faults as required in 8.2 shall be
capable of being reset
a
automatically when faults are no longer recognized,
and/or
b
by a manual operation at access level 2.
8.7.2 Following reset as specified in 8.7. 1 , the indication of
the correct functional conditions corresponding to any
received signals shall either remain or be re-established
within 20 s.
8.8 Transmission of the fault warning condition
The VACIE shall have provision for transmitting, by means
of at least general fault signal, all faults specified in 8. This
fault signal shall also be given if the VACIE is de-energized.
Bosch Security Systems B.V.
Compliance
Since the Praesideo system does not offer automatic reset
from the fault warning condition this requirement does not
need to be implemented.
After the audible indication has been silenced (by
acknowledging all faults) the Praesideo system will resound
the indication upon occurrence of a new fault or
reoccurrence of a previously resolved fault.
Praesideo is compliant.
The Praesideo system does not offer automatic reset of
faults
Faults can be manually reset by acknowledging and
resetting them individually or all in one action.
Acknowledging and/or resetting faults individually can be
done via the front panel menu of the Network Controller
and via the Open Interface. Acknowledging and/or
resetting all faults in one action can be done via the front
panel menu of the network controller, control input
contacts, call station keys or the Open Interface.
A fault reset is processed by Praesideo within 20 s to
update the status of all fault indicators. Praesideo will enter
the fault warning condition again within 100 s of the
occurrence of a new or still unresolved fault.
Praesideo is compliant.
Output contact 5 of the Praesideo network controller is the
fixed Fault alarm indicator output. This relay output contact
indicates no fault when open (energized) and indicates a
fault when closed (de-energized). If the Praesideo system is
de-energized this output contact is closed, therefore the
fault signal will also be given.
Manual de uso e instalación
Signature
IUI-PRAESIDEO_4.3 | V1.0 | 2015.02
es | 59
Tabla de contenido
loading

Tabla de contenido