Combustion
Let the burner run at full capacity for about ten minutes, setting all
the elements correctly as explained in this manual.
Then carry out the analysis of the combustion by checking:
CO2 percentage (%);
CO content (ppm);
NOx content (ppm);
Ionisation current (µA);
Flue gas temperature at the flue.
Adjust the burner if the combustion values found at the beginning
of the operation do not comply with the regulations in force or, at
any rate, do not produce good combustion.
Use the appropriate card to record the new combustion values;
they will be useful for subsequent controls.
20123803
Maintenance
7.2.4

Safety components

The safety components must be replaced at the end of their life
cycle indicated in Tab. F. The specified life cycles do not refer to
the warranty terms indicated in the delivery or payment
conditions.
Safety component
Flame control
Flame sensor
Gas valves (solenoid)
Pressure switches
Pressure adjuster
Servomotor (electronic
cam) (if present)
Oil valve (solenoid) (if
present)
Oil regulator (if present)
Oil pipes/ couplings
(metallic) (if present)
Flexible hoses (if present)
Fan impeller
22
GB
Life cycle
10 years or 250,000
operation cycles
10 years or 250,000
operation cycles
10 years or 250,000
operation cycles
10 years or 250,000
operation cycles
15 years
10 years or 250,000
operation cycles
10 years or 250,000
operation cycles
10 years or 250,000
operation cycles
10 years
5 years or 30,000 pressurised
cycles
10 years or 500,000 start-ups
Tab. F