Adapting The Unit To The Mains Voltage - Pfannenberg DTT 6301 Serie Manual De Instrucciones

Ocultar thumbs Ver también para DTT 6301 Serie:
Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 314
ENG
4.6.8

Adapting the unit to the mains voltage

Factory settings upstream transformer
Fig. 25: Adapting the mains voltage on the upstream transformer
Units with a mains voltage of 400/460 V can be connected optionally to another mains voltage.
The mains voltage on the upstream transformer must be adapted for this.
The adaption is made by replugging the supply cable on the primary side of the transformer.
The upstream fuse must match the changed mains voltage, see the "Upstream fuse" column in
The data for the transformer factory settings can be found on the yellow connection diagram (1) on the rear of the unit.
UL-conform with following fuses: Category "Class CC", slow-blow, suitable for transformer protection.
Mains voltage
400 V
440 V
460 V
Tab. 9: Transformer options and upstream fuse
NOTE
The changed mains voltage on the transformer must be marked on the yellow connection diagram (1) on the back of the unit.
Operating Manual | Roof-mounted Cooling Unit | Multi Controller (MC) – 400 / 460 V, 3~ | 086100033c
Transformer input
winding
T1/ 1 [0] – T 1/ 2 [400]
T1/ 1 [0] – T 1/ 3 [440]
T1/ 1 [0] – T 1/ 4 [460]
L2
L1
Input winding upstream transformer
Upstream fuse (min. 480 V)
DTx 6201
Max. 5 A
Max. 5 A
Max. 5 A
G00056
Tab. 9
DTx6301
Max. 6 A
Max. 6 A
Max. 6 A
50/51