3.4.10

Multimaster function

Fig. 11: Multimaster Control
The Multimaster function can control up to six cooling units in the system (bus function). Several cooling units are connected
with each other by a 2-wire bus for this.
Functional description
In the bus function, the cooling unit that reaches the switching threshold "T
It is ended by the cooling unit that drops below the switching threshold "T
The energy-saving mode is ended by the cooling request of one of the cooling units in the bus function.
The energy-saving mode is reactivated 30 minutes (delivery condition) after the last cooling request of one of the cooling
units in the bus function.
If the minimum temperature alarm is triggered (Lit_, falling below the lower temperature limit), check the affected unit. If
the unit is part of a Multimaster system, the cooling requirement can be forced from another unit. If this is the case, the
proper functioning of each unit involved in Multimaster operation must be checked.
NOTE
All cooling units in the bus function can activate or end the cooling mode or the energy-saving mode. There is no
"master and slave function".
For details of the electrical connection, see section "Multimaster Control", Page 43.
Operating Manual | Roof-mounted Cooling Unit | Multi Controller (MC) – 230 V | 086100019c
+ 2K" first activates the cooling mode.
nom
- 2K" last.
nom