en - Original instructions

3.3 Application Setup

3.3.1 Select Operating Mode

Select operating mode based on your system.
Operating Mode
CHANGING OPERATING
MODE WILL OVERWRITE
CURRENT SETUP
Single Pump Control
Operating Mode
CHANGING OPERATING
MODE WILL OVERWRITE
CURRENT SETUP
Multipump Control
Operating Mode
CHANGING OPERATING
MODE WILL OVERWRITE
CURRENT SETUP
Speed Control
3.3.2 Single Pump Control
Example for Constant pressure, low power rate pump.
Application Type
Constant Pressure
Pressure Control Units
Ramp Time
Regulation Band
Would you like to Autoset
the rest of the settings?
Constant Pressure
Default Values Loaded
28
bar
Fast
20%
Yes
Setpoint
3,5 bar
(See IOM)
[OK]
1. Single Pump Control (continue to
Control.
2. Multi-pump Control (continue to
control)
3. Speed Control for fixed speed application (contin-
ue to
Speed
Control)
1. Selectable applications are Constant Pressure,
Flow Control and Level Control. Refer to the full man-
ual for details.
2. Select Pressure Control Unit.
3. Select Ramp Time. See
for details.
4. Set desired pressure regulation band for Double
Ramp Control Logic. See
for details.
5. Select Yes to Autoset the rest of the settings. See
Autoset Parameters Extract
6. Set desired setpoint.
7. Default Value Loaded. Press OK to continue.
Single Pump
Multi-pump Multi-
Ramp Control description
Ramp Control description
for details.