GENERAL FEATURES & TECHNICAL INFORMATION
General Features:
In the event of a sudden loss of the cold water supply, the hot water supply will be cut-off (response time
is 2 seconds) if the mixed water temperature selected is less than 42°C. Filters and non-return valves
at the mixer inlets protect the thermostat and prevent any back-flow into the pipework system.
Note: If, instead of cold water, the hot water returns through the mechanical mixer, there is no anti-scald
fail safe. We recommend installing a non-return valve on the cold water inlet of the mechanical mixer.
Technical Information:
• The factory pre-set is 38°C, with a temperature differential of 50°C between the cold and hot water.
• Range of mixed water settings: from 25°C to 40°C for H9739 and H9739S, and from 25°C to 41°C
for H9741, H9741S, H9741TP and H9752S. The maximum temperature is set at 38°C for H9739,
H9739S and H9741TP. Models H9741, H9741S and H9752S can be set at 41°C by pressing
on the button on the control knob , (Fig. C).
• Maximum hot water temperature: 85°C.
• Min./max. pressure: 1 to 5 bar (recommended 3 bar). Difference in pressure at water entry point:
max. 1bar.
• Safety: hot water shut-off in the case of loss of cold water. The hot water fail-safe is active
if the difference in temperature between the hot water and the cold water is more than 15°C.
• Flow rate regulated at 9 lpm.
• Temperature adjustment control is on the left and the flow-rate control is on the right.
INSTALLATION (Fig. A and B)
2 off-set connectors enable adjustable pipe-centres (150mm +/-20).
Mixers supplied with standard connectors:
1. Using PTFE or a waterproof sealant on the ½" threaded connector , tighten offset connectors
at right angles to the wall. Ensure a waterproof seal between the supply pipes and the finished wall.
2. Mount the offset connectors  ensuring that the mixer is horizontal. Tighten the cover plates 
onto the offset connectors  by hand.
3. Fit the filters supplied in the turning lock-nuts (for H9741, H9741S, H9752S and H9752P
they are integrated in the lock-nuts) and mount the mixer on the offset connectors so that
the hot water is delivered from the left and exits from the bottom outlet.
Mixers supplied with STOP/CHECK connectors (ref. 855755.2P/855755UK.2P): please see installation
guide supplied with connectors.
REMEMBER
• Our mixers must be installed by professional installers in accordance with current regulations
and recommendations in your country, and the specifications of the fluid engineer.
• Sizing the pipes correctly will avoid problems of flow rate, pressure loss and water hammer
(see calculation table in our brochure and online at www.delabie.com).
• Protect the installation with filters, water hammer absorbers and pressure reducers to reduce
the frequency of maintenance (recommended pressure from 1 to 5 bar maximum).
• Install stopcocks close to the mixer to facilitate maintenance.
• The pipework, filters, non-return valves, stopcocks, bib taps, cartridge and all sanitary fittings should
be checked at least once a year, and more frequently if necessary.
EN