Technical data
3.7.1
Refrigeration circuit
Designation
Cooling capacity at A35 / A35 */**
Cooling capacity at A45 / A35 */**
Refrigerant type *
Refrigerant quantity *
Temperature setpoint (factory setting)
Fault indication Switch cabinet interior temperature
(factory setting)
Ambient air temperature
Switch cabinet interior temperature
Air volume flow, exterior circuit
Air volume flow, interior circuit
Condensate separation
Tab. 3: Refrigeration data
*
Data on the type plate.
**
The use of optional filter mats reduces the cooling capacity
3.7.2
Electrical data
Designation
Rated operating voltage */****
Rated frequency *
Functional area
Power consumption * A35/A35*
Power consumption condensate evaporator
Nominal current *
Start-up current*
*
Data on the type plate.
***
Max. rated current UL at 60 Hz.
****
Adapt upstream fuse when rated voltage changes, see "Adapting the unit to the mains voltage", Page 39.
Operating Manual | Attachment and Installation Cooling Units | Standard Controller (SC) – 230 V | 086100005e
Q
0
Q
0
P
50 Hz
el
P
60 Hz
el
P
el
I
50 Hz
nom max
I
60 Hz
nom max
I
Start max
Model DTI / DTS 6401
2000 W
1440 W
R134a
1200 g
+35 °C (+95 °F)
SC-Controller: > +50 °C (+122 °F)
MC-Controller: > +52 °C (+125.6 °F)
+15 °C (+59 °F) to +55 °C (+131 °F)
+25 °C (+77 °F) to +45 °C (+113 °F)
1175 m³/h
885 m³/h
Condensate evaporator
Model DTI / DTS 6401
230 V, 1~
50 / 60 Hz
DIN IEC 60038
1047 W
1273 W
30 to 110 W (A35 / A35 approx. 70 W)
5.45 A
6 A / 6 A***
21.4 A
19/58