GB
2.6
Technical data
2.6.1
Refrigeration data
Designation
Cooling capacity A35 / A35 * / **
Cooling capacity A50 / A35 * / **
Refrigerant type *
Refrigerant amount *
Thermostat setting (factory set)
Failure indication: Enclosure internal
temperature (factory set)
Ambient air temperature
Enclosure internal temperature
Air volume, external circulation
Air volume, internal circulation
Condensation discharge
Sound pressure level (1m)
2.6.2
Electrical data
Designation
Rated
operating
voltage * / ***
Rated frequency *
Operating range
Power consumption *
Rated current*
Starting current*
2.6.3
Dimensions
Designation
Height
Width
Depth with cover (standard)
Weight
Installation attitude
Unit construction
2.6.4
Other unit data
Designation
Corrosion protection
Protection classification
*
Data on the type plate.
***
With a change to the rated operating voltage, see
Operating Manual DTT 6601 Multicontroller (MC) 086100037 © Pfannenberg GmbH
Model DTT 6601
50 Hz
Q
3000 W
0
Q
2000 W
0
1970 m³/h
1420 m³/h
Model DTT 6601
400V/ 50 Hz
P
el
1700 W
A35/A35
I
3,16 A
nom max
I
8,9 A
Start max
Model DTT 6601
75 kg
Model DTT 6601
Standard: Galvanized, electrostatically powder coated
Option: Stainless steel unit hood
Under correct operating conditions:
IP 54 against the enclosure (EN 60529).
IP 34 against the environment (EN 60529).
**
Use of optional filter mats reduces the cooling capacity.
Adapting the
60 Hz
50 Hz
3200 W
4000 W
2250 W
3260 W
R 134a
1250 g
+35°C (+95°F)
> +50°C (+122°F)
+15°C (+59°F) bis +55°C (+131°F)
+25°C (+77°F) bis +45°C (+113°F)
2180 m³/h
1970 m³/h
1530 m³/h
1420 m³/h
Condensate evaporator
≤ 62 dB(A)
400 / 460 V 3~
50 / 60 Hz
DIN IEC 60038
460V/ 60 Hz
400V/ 50 Hz
2100
1601
4,5 A
4,6 A
9,9 A
17,1 A
485 mm
795 mm
575 mm
Vertical
Standard: Steel/ plastic
upstream fuse /transformer options
Model DTT 6801
60 Hz
4250 W
3495 W
2180 m³/h
1530 m³/h
Model DTT 6801
460V/ 60 Hz
1989
4,5 A
19,5 A
Model DTT 6801
77 kg
Model DTT 6801
(200°C)
.