Configuration; Functional Check - Siemens REV200RF/SET Manual De Usuario

Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 14
7
Finish mounting of REV-R.03...
a)
Switch off power
b)
Mark location where REV-R.03... is currently fixed
DIP-switch Configuration and functional check REV200...RF
1

Configuration

1.1.
Calibrating the sensor: DIP-switch 9
After activating the DIP-switch the CAL symbol will be shown and the
actual room temperature currently measured will flash. With pressing
+
the
can now be recalibrated by a maximum ± 2 °C. To store
the recalibration, press the set button (also refer to Fig.11/F).
1.1.2
Setpoint limitation: DIP-switch 3
There are 2 setting choices available:
OFF. 3...29 °C (factory setting) or ON 16...29 °C
To store press the set button (also refer to Fig.11/B)
1.1.3
Optimum on; DIP switches 6 to 8
Optimum on brings forward the switch on point P.1 such that the
selected set value will be reached at the desired time. The setting
depends on the type of control system, that is, on heat transmission
(piping system, radiators), building dynamics (building mass,
insulation) and heating output (boiler output, flow temperature).
(Also refer to Diagram in Fig. 11/E)
OFF
No effect (standard setting)
¼ h/°C
For fast controlled systems
½ h/°C
For medium controlled systems
1 h/°C
For slow controlled systems
Legend to diagram for Fig. 11/E:
T
Temperature (°C)
t
Forward shift of switch-on point (h)
TRx
Actual value of room temperature
Pon
Starting point for optimum on
1.1.4
Control mode; DIP switches 1 and 2
DIP-switch 1 OFF and DIP-switch 2 OFF
Adaptive control (standard) for all normal conditions
DIP-switch 1 OFF and DIP-switch 2 ON
Normal controlled systems for situations with normal
temperature variations
DIP-switch 1 ON and DIP-switch 2 OFF
Fast controlled systems for situations with great
temperature variations
DIP-switch 1 ON and DIP-switch 2 ON
Difficult controlled systems, proper on/off controller with a
switching differential of 0.5 °C
(also refer to Fig.11/A).
8/30
09.02.2007
c)
d)
e)
1.1.5
This function protects the pump against seizing during longer off
periods. Periodic pump run is activated for a minute every 24 hours
at 12:00 (when pump run is activated, the flame symbol
appears on the display). To store press the set button (also refer to
Fig.11/D).
DIP-switch 5 OFF (Standard)
DIP-switch 5 ON
Only useable with controled cirulating pumps.
1.1.6
DIP-switch 4 OFF (Standard) for heating
DIP-switch 4 ON for cooling
(also refer to Fig.11/C)
2
a) Check the display. If there is no display, check the correct fitting
b) Operating mode
c) In the case of heating mode, set the set value temperature to
d) The relay and thus the regulating unit must respond after no
e) Reset set value temperature
3
Self learning
User-defined data:
Press the button behind the pin opening for at least one second:
PID 12
this resets the user-specific settings to their default values. The
clock starts at 12:00. During the reset time, all sections of the
display light up, enabling them to be checked.
PID 6
4
2-Pt
G2214xx
If necessary loosen wiring
Mount receiver at location marked before according Fig. 12 to
14, wire completely and close housing
Switch on power
Periodic pump run DIP-switch 5
Heating / cooling mode DIP-switch 4

Functional check

and function of the batteries.
.
29 °C .
more than 1 minute the symbol
this is not the case:
Check regulating unit and wiring
Room temperature may be higher than 29 °C.
mode 19 °C,or your individual temperature).
Reset
Notes
The controler conforms to "Software Class A" and is for use in
"normal" pollution situation
REV200...RF/SET is a set of units consisting of electric room
temperature controller/thermostat with a weekly timeswitch and
transmitter (REV200...RF) and a RF receiver (REV-R.03...)
Building Technologies / HVAC Products
appears on the display. If
to its previous level (heating
Tabla de contenido
loading

Este manual también es adecuado para:

Rev200srf/set

Tabla de contenido