P
OWERING ON FOR THE
➢ If present, set the "1/0" switch to "1" and wait for a few seconds. Check
that the display is turned on and the CPS enters "STAND-BY" mode.
Check that no error messages appear indicating that the input cables do not respect the correct phase direction. In
this case, the following operations should be performed:
▪
Switch off the CPS by moving the "I/0" switch to "0" (if present), and open all the input and output disconnecting
switches.
▪
Wait for the display to go off.
▪
Open the battery fuse holders.
▪
Open all the protective devices upstream from the CPS
▪
Remove the panel covering the input terminal board
▪
Correct the position of the input wires so that the phase direction is respected.
only if the separate bypass option is present: check which terminal board (input and/or bypass) the error code
shown on the display corresponds to (see the "Alarm Codes" paragraph); correct the position of the wires of the
terminal board indicated so that the phase direction is respected
▪
Close the panel again
▪
Repeat the power-on operations including the "preliminary operations"
➢ Press
the start menu. Choose Yes when prompted to confirm. Press
wait for a few seconds. Check that the CPS is set with the load
powered by the inverter.
➢ Open the input switch (SWIN) and wait for a few seconds. Check that
the CPS goes into battery-powered mode and that the load is still
powered correctly. A beep should be heard approximately every 7
seconds.
➢ Close the input switch (SWIN) and wait for a few seconds. Check that
the CPS is not in battery-powered mode and that the load is powered
correctly by the inverter.
➢ To set the Date and Time, access menu 8.6.7 (see "Display menus").
Use the up/down arrows (↑↓) to set the desired value and then confirm
with the
move to the next field. To save the new settings, go back to the
previous menu by pressing the
F
T
IRST
IME
to confirm and
key.
- 87 -
to enter
key to