EAS ELECTRIC ECH Serie Manual De Instalación página 81

Tabla de contenido
Idiomas disponibles

Idiomas disponibles

8.2 Ordinary displayed data
a. Ordinary displayed data are displayed in all display pages.
b. If the unit system is under running state, i.e. one or more than
one Modular unit is under running operation, there will be a
dynamic display of
. If the system is under OFF state, there
is no display.
c. If the communication with the main unit Modular unit is fail, it
displays E2
d. If it is under the host computer network control,
otherwise there is no display.
e. If it is under wired controller locked or button locked state, it
displays
the lock mark. There will be no display after the lock
is unlocked.
8.3 Treatment of display data
The data display area is divided into Up area and Down area,
with two groups of two-digit half 7-segment digital display,
respectively.
a.Temperature display
Temperature display is used for displaying the total outlet water
temperature of unit system, outlet water temperature ,condenser
pipe temperature T3A of system A, condenser pipe temperature
T3B of system B, outdoor environmental temperature T4,
anti-freezing temperature T6 and setting temperature Ts, with
allowable data display scope -15℃~70℃. If the temperature is
higher than 70℃, it is displayed as 70℃. If there is no effective
date, it displays "— —" and indication point
b. Current display
Current display is used for displaying Modular unit system A
compressor current IA or system B compressor current IB, with
allowable display scope 0A~99A. If it is higher than 99A, it is
displayed as 99A. If there is no effective date, it displays "— —"
and indication point
A
is on.
c. Failure display
It is used for displaying the total failure warning date of unit or
that of Modular unit, with failure display scope E0~EF, E
indicating failure, 0~F indicating failure code. "E-" is displayed
when there is no failure and indication point
time.
d. Protection display
It is used for displaying the total system protection data of unit or
the system protection data of Modular unit, with protection
display scope P0~PF, P indicating system protection, 0~F
indicating protection code. "P-" is displayed when there is no
failure .
e. Unit number display
It is used for displaying the address number of the currently
selected Modular unit, with display scope 0~15 and indication
point
#
is on at the same time.
f. Display of online unit number and startup unit number
They are used for displaying the total online Modular units of the
whole unit system and the number of the Modular unit under
running state, respectively, with display scope 0~16.
Any time when the spot check page is entered to display or
change Modular unit, it is needed to wait for the up-to-date data
of the Modular unit received and selected by wired controller.
Before receiving the data, the wired controller only displays
"——" on the data display Down area, and the Up area displays
the address number of the Modular unit. No page can be turned,
which continues until the wired controller receives the
communication data of this Modular unit.
V.2
24
Net
displays,
C
is on.
#
is on at the same
8.4 Query display
Press the "▲" or "▼" key of wire controller to adjust the main unit
serial number can query 16 sets main units' status information from
#0~#15. Press "
" or "
number of one main unit then can query all the status information of
this unit.
Spot check content according to the main unit model wired controller:
No.
Spot inspection item
Standby: ODU address (L88) + number of on-line units
(R88),
On: display frequency
0
Defrosting: dF and operating frequency flash alternately
at 1s intervals
In case of Pb protection, Pb and operating frequency
flash alternately at 1s intervals
1
0.xx
ODU address
2
1.xx
ODU Hp
3
2.xx
Number of ODUs (Main unit included)
4
3.xx
T4 capacity revision
Operation modes (8 OFF, 0 Standby, 1 Cooling, and 2
5
4.xx
Heating)
6
5.xx
Fan Speed 1
7
6.xx
Fan Speed 2
8
7.xx
T3
9
8.xx
T4
10
9.xx
T5
11
10.xx Taf1
12
11.xx Taf2
13
12.xx Tw
14
t.xx
Twi unit water inlet (displays to decimal places)
15
14.xx Two unit water outlet
16
15.xx Tz general cold water leaving temperature
17
16.xx THeatR heat recovery sensor temperature
18
17.xx Air discharge 1
19
18.xx Air discharge 2
20
19.xx Heat sink temperature 1
21
20.xx Heat sink temperature 2
22
21.xx Air discharge superheat degree DSH
23
22.xx Current of compressor A
24
23.xx Current of Compressor B
25
24.xx Water pump current
26
25.xx Electronic expansion valve 1 opening (/4)
27
26.xx Electronic expansion valve 2 opening (/4)
28
27.xx High pressure
29
L.xx
Low pressure (displays to decimal places)
30
29.xx Air return superheat degree
31
30.xx Air return temperature
32
31.xx Mute selection
33
32.xx Static pressure selection
34
33.xx DC voltage A (reserved)
35
34.xx DC voltage B (reserved)
36
35.xx Last fault
Limit frequency No. (0: no limits; 1: T4 limit frequency; 2:
voltage limit frequency; 3: air discharge limit frequency;
4: low voltage ratio; 5: instant limit frequency; 6: current
37
36.xx
limit frequency; 7: voltage limit frequency; 8: pressure
ratio and capacity demand adjusting; 9: cooling low
pressure limit frequency)
Defrosting process status (the first digit: T4 selection
38
37.xx
solution; the second digit: scheme's range; the third and
fourth digits as a whole indicates the defrosting time)
E-direction failure: 1 indicates failure, and 0 indicates no
39
38.xx
failure
40
39.xx Defrosting scheme
41
40.xx Initial frequency
42
41.xx Tc
43
42.xx Te
44
43.xx ----
" to adjust the spot check sequence
Tabla de contenido
loading

Este manual también es adecuado para:

Ech-030nvtbi

Tabla de contenido