Use Conditions Of The Unit - EAS ELECTRIC ECH Serie Manual De Instalación

Tabla de contenido
Idiomas disponibles

Idiomas disponibles

OPERATION & PERFORMANCE
Performance characteristics of the unit
The air-cooled heat pump Modular unit is composed of one or more modules. Each module has its own independent electric
control unit, and the electric control units of modules conduct information exchange through communication network. The
air-cooled heat pump Modular unit is characteristics of compact structure and easy transportation and lifting, and in the meanwhile,
it also saves facilities, including cooling tower, cooling pump, and so on, for the user, and reduces installation cost.
The units provide central air handling devices or terminal equipment with chilled water or hot water. The unit is a completely
independent entirety type one, which is designed to be installed outdoors (on the ground or the roof). Each unit includes such main
parts as high-efficient and low-noise Modular compressor, air-cooled condenser, shell and tube (or plate) evaporator,
micro-computer control center, and so on. These parts are installed on steel structure base, so they are sound and durable.
The unit applies Chinese micro-computer control system, which can automatically conduct energy control according to the
magnitude of load, to achieve optimal matching and thus actually realizing optimal energy-saving operation. The product is
Modularized unit, and parallel connection of 16 modules can be realized at most, so the user can adopt module combination
according his own demands. The product can be widely applied in air-conditioning engineering of various newly-built and rebuilt
industrial and civil buildings, such as restaurant, hotel, apartment, office building, hospital, industrial plant, and so on. The
air-cooled heat pump Modular unit is the best choice for the place which has high requirement in noise and ambient environment
and which is short of water.
The A-weighted sound pressure level is below 70 dB.

Use conditions of the unit

a. The standard voltage of power supply is 380-415V 3N~50Hz, the minimum allowable voltage is 342V, and the maximum voltage is
456V.
b. To maintain better performance, please operate the unit under the following outdoor temperature:
ECH-030NVTBI
ECH-060NVTBI
Ambient
temperature
43
35
25
15
5
-5
-15
0
Cooling operating range
If the user requires the unit to operate under the outlet water temperature is lower than
the minimum setting value mentioned above, be sure to make the requirement to the dealer or
our maintenance center, and necessary protective measures should be taken before the unit
is used.
V.2
5
10
15
20
(Unit:℃) Outlet water
temperature
ECH-030NVTBI
ECH-060NVTBI
Ambient
temperature
30
0
-4
-7
-10
-15
25 30 40 45 50 52 55
Heating operating range
(Unit:℃)
Outlet water
temperature
1
Tabla de contenido
loading

Este manual también es adecuado para:

Ech-030nvtbi

Tabla de contenido