Function Of Terminals - EAS ELECTRIC ECH R32 Serie Manual De Instalación Y Usuario

Ocultar thumbs Ver también para ECH R32 Serie:
Tabla de contenido
Idiomas disponibles

Idiomas disponibles

8.5.7 Requirements for power cord connection
Correct
L1
L2 L3
L1
L2
L3
16
Wrong
L1
L2 L3
L1
L2
L3
N
Fig. 8-11 Requirements for power cord connection
NOTE
Please use the round-type terminal with correct specifications to
connect the power cord.
N
N
N

8.5.8 Function of terminals

As shown in the figure below, the uint communication signal wire
is connected to the terminal block XT2 at 5(X), 6(Y) and 7(E), and
the wired controller signal wire is connected at 8(X), 9(Y) and
10(E) inside the electric control box. For specific wiring, see
chapter 8.5.13.
XT2
Uint communication
Fig. 8-12 Wiring of unit communication and
the wired controller communication
When the water pump and auxiliary heater are added externally,
a 3-phase contactor must be used for control. The model of
contactor is subject to the power of water pump and heater
power. The contactor coil is controlled by the main control board.
See the figure below for coil wiring. For specific wiring, see
chapter 8.5.13 .
The user can connect an ac light to monitor the state of
compressor.When the compressor is operating,the light will be
powered on.
The wiring of water pump and pipeline auxiliary heater and ac light
of the state of compressor is as follows.
XT1
HEAT1
Coil of
3 phase
AC contactor
L1/L2/L3
220-240V~
50Hz
N
Fig. 8-13 Wiring of water pump and pipeline auxiliary heater
and ac light of the state of compressor
8.5.9 Wiring of "ON/OFF" weak electric port
The remote function of "ON/OFF" must be set by DIP switch .The
remote function of "ON/OFF" is effective when S5-3 is chosen ON,
at the same time, the wired controller is out of control.
Corresponding parallel connect the "ON/OFF" port of the main
unit's electric control box,then, connect the "ON/OFF" signal
(provide by user) to the "ON/OFF" port of main unit as follows.
The remote function of "ON/OFF" must be DIP switch set.
Wiring method: Shorting the terminal block XT2 at 15 and 24
inside the electric control box to enable the remote function of
"ON/OFF" .
20
The wired controller
communication
COM
COMP-STATE
PUMP
N
Coil of
3 phase
AC contactor
Max voltage:240VAC
Max current:5A
V.1

Capítulos

Tabla de contenido
loading

Este manual también es adecuado para:

Ech030nhrEch060nhr

Tabla de contenido