Figure 4 — 120/240 Volt AC, 20 Amp Receptacle
4-Wire Cord Set
Y (Hot)
NEMA L14-20
This receptacle powers 120/240 Volt AC, 60 Hz, single
phase loads requiring up to 3,550 watts of power
(3.55 kW) at 20 Amps for 120 Volts or 240 Volts.The outlet
is protected by a push–to–reset circuit breaker.
CAUTION!
Although this outlet states it has a
120/240 Volt 20 Amp rating (up to 4,800 watts), the
generator is only rated for up to 3,550 watts.
Powering loads that exceed the wattage/amperage
capacity of the generator can damage it or cause
serious injuries.
120 Volt AC, 20 Amp, Duplex
Receptacles
Each duplex receptacle (Figure 5) is protected against
overload by a push–to–reset circuit breaker.
Figure 5 — 120 Volt, 20 Amp Duplex Receptacle
240V
120V
120V
W (Neutral)
X (Hot)
Ground (Green)
Section 4: Operation
Use each receptacle to operate 120 Volt AC, single–phase,
60 Hz electrical loads requiring up to 2,400 watts (2.4 kW)
at 20 Amps of current. Use cord sets that are rated for
125 Volt AC loads at 20 Amps (or greater).
CAUTION!
These outlets are rated at 120 Volt
20 Amp each (up to 80 Amps).The generator may
only be rated for up to 29.6 Amps. Powering loads
that exceed the wattage/amperage capacity of the
generator can damage it or cause serious injuries.
COLD WEATHER
OPERATION
Under certain weather conditions (temperatures below
40°F [4°C] and a high dew point), your generator may
experience icing of the carburetor and/or the crankcase
breather system.
Build a structure that will enclose three sides and the top
of the generator:
1.
Make sure entire muffler-side of generator is exposed.
Note generator may appear different from that shown
in Figure 7.
Figure 7 — Permanent Cold Weather Shelter
Wind
2.
Ensure a minimum of two feet clearance between open
side of box and nearest object.
3.
Face exposed end away from wind and elements.
4.
Enclosure should hold enough heat created by the
generator to prevent problems.
CAUTION
! NEVER run unit indoors. DO NOT
enclose generator any more than shown. Remove
generator from shelter when temperature is above
40°F [4°C].