11.6.4 Setting the controller parameters
1. Select a controller in the "setup" menu and
configure it.
See section
11.6 Selection, configuration and
parameterisation of the
controller.
2. Select the line "controller" in "main menu" using
the [Up] and [Down] buttons, and press [OK] to
switch to the "controller" menu.
See section
11.4 Main
menu.
main menu
controller
i.e.
interpulse
relay 1
control
relay 2
cont.controll
er
Fig. 31
Setting the controller parameters
The options available in the "controller" submenu
(main menu) correspond to the configuration made in
the "setup" menu.
1. Use the [Up] and [Down] buttons to change
internal setpoints within the selected measuring
range.
See section
8.4 Measuring
36
setpoint
setpoint
internal
prop.band XP
reset time TN
deriv.action TV
int.pulse period
min.switch-on
constant load
max.dosing flow
adaptation
adjustments, see above and section
adjustments, see above and section
ranges.
The "controller" option in "main menu" is
only available if a controller has been
selected in the "setup" menu!
Note
Example:
Configured limit contact or two-position
controller and activated continuous
controller.
setpoint
0-20 mA / 4-20 mA
external
chlorine 0.00-20.00 mg/l
pH 0-14.00 pH
0.0 to 3000.0 %
1 to 3000 s
1 to 1000 s
1 to 100 s
0.1 to 10.0 s
0 to 50 %
0 to 100 %
start
stop
adapt.result
8.3
8.2
2. Select the displayed controller parameters using
the [Up] and [Down] buttons, press [OK] to switch
to the desired submenu, and use the [Up] and
[Down] buttons to adjust the setpoints as needed
within the permitted ranges.
See section
8.3.3 Controller
functions.