12 QC04 Smart Module Intinsically safe
12.1
Product marking
Control Module
Type Label
Terminals
Fig 14. Product marking
ATEX
Hazardous or Classified Location
0344
II 1 GD Ex ia IIC T4 T80°C IP65
KEMA 02ATEX1242X
Ta = -20°C...+50°C (-4°F...122°F)
Hazardous or Classified Location
APPROVED
Intrinsically safe, Class I, II, III Div.1,
Groups ABCDEFG, T4, Type 4X/IP65
Class I, Zone 0, AEx ia IIC T4, IP65,
Ta = -20°C...+50°C (-4°F...122°F)
Hazardous or Classified Location
Intrinsically safe, Class I, II, III Div.1,
Groups ABCDEFG, T4
Ex ia IIC T4, IP65, (Class I, Zone 0/1)
Ta = -20°C...+50°C (-4°F...122°F)
DOC.IG.QC01.1 Rev.: B
12.2
ATEX Intended use
The Control Module QC04..P1.. of the FieldQ
pneumatic actuator are Group II category 1
equipment and intended for use in areas in which
explosive atmospheres caused by mixtures of air
and gases, vapours, mists or by air/dusts are likely
to occur.
The pneumatic actuator part, together with the
pneumatic Module part of the FieldQ pneumatic
actuators is a Group II category 2 equipment and
intended for use in areas in which explosive
atmospheres caused by mixtures of air and gases,
vapours, mists or by air/dusts are likely to occur.
Therefore it may be used in (ATEX) classified
Zones 1, 2 (Gasses) and/or 21, 22 (Dust).
12.3
Special conditions for safe use
(ATEX).
The material for the Control Module housing is an
aluminum alloy. When the unit is used in a
potentionally explosive atmosphere, requiring
ATEX equipment category 1 G, the unit must be
installed in such a way, that even in the event of
rare incidents, an ignition source due to impact or
friction between the enclosure and iron/steel.
For applications in explosive atmospheres caused
by air/dust mixtures and where category 1D
apparatus is required, the surface temperature has
been determined for a dust layer with a thickness
of 5 mm maximum.
12.4
Dielectric strength
Control Module QC04 complies to the dielectric
strength requirement according IEC- 60079-11
QC03 Intrinsically Safe Entity Parameters
Circuit
Terminal Ui
Power Supply
7-8
Control input
5-6
Feedback 1
3-4
Feedback 2
1-2
14
Ii
Pi
Ci
30VDC 300mA 1.2W 15 nF
30VDC 300mA 1.2W 15 nF
30VDC 300mA 1.2W 18 nF
30VDC 300mA 1.2W 18 nF
December '06
Li
0
0
0
0
Tabla de contenido