Johnson Controls tyco 3G4000W Manual página 32

Tabla de contenido
Idiomas disponibles

Idiomas disponibles

Alarm Restore SIA Reporting Code: This option is dependent on whether SIA or Contact ID has
been selected for the communicator's reporting format. If SIA is selected, the reporting code used
for the zone alarm restore condition can be modified using this entry. Zones use default reporting
codes, so this entry doesn't typically need to be programmed.
End of Line: This option determines whether the zone input is configured as Normally Open,
Normally Close, or Single End of Line:
• A normally open setting creates an alarm condition when the input is shorted and restores when
the circuit is open.
• A normally closed setting creates an alarm condition when the input is open and restores when
the circuit is shorted.
• A single end of line setting creates an alarm condition when the input is open or shorted, and
restores when the loop resistance is 5.6K ohms. Use a 5.6k resistor in this configuration.
Configure this setting as Not Used if the zone input is not required.
Zone Follows Delay Timer Enabled: There are 2 settings available for this option, No Delay or
Follows Delay Time. This timer only applies to zones that are configured as AC Power Trouble. An
AC power trouble is generated only if it persists for the full duration of the timer, at which time it is
communicated to the central station. If the zone input restores before the delay timer has expired
then the signal is not communicated to the central station. After the 3G4000W communicates the
AC Failure reporting code, the zone must restore for the full duration of the delay timer before an
AC Restore signal is communicated to the central station.
Zone Delay Timer: Default (0 minutes)
This setting is used in conjunction with the Zone Follows Delay Timer function and determines the
time, in minutes, that the zone must be violated or restored before an AC Power Trouble or AC
Power Trouble restore reporting code is communicated to the central station. Typically a value of
2 minutes is sufficient to eliminate transmissions of temporary power failures. If the power failure
continues longer than the programmed duration the AC Power Trouble reporting code is sent. The
power failure must also be restored for the programmed duration before the AC Power Trouble
Restore reporting code is sent.
Send on Violation Enabled: Default (Enabled)
When this option is disabled, reporting codes are not sent to the central monitoring station when
the zone is in an open or violated state. Zone alarm signals are reported to the central station when
this option is enabled.
Send on Restore Enabled: Default (Enabled)
When this option is disabled, reporting codes are be sent to the central monitoring station when
the zone is in a closed or restored state following an alarm condition. Zone alarm restore signals
are reported to the central station when this option is enabled.
Zone Monitors Panel Arm Status: This option is used in conjunction with the SMS command and
control feature. An output of the control panel must be programmed as Armed Status and wired
to this zone input. SMS messages can then be sent to the communicator to determine whether the
zone is open or closed, which represents whether the alarm system is armed or disarmed.
This feature overrides the zone type settings.
Zone Input 1 or 2 Status: This entry reflects the current status of the zone inputs the last time a
DLS upload was performed. Zone status is indicated as opened or closed.
32
3G4000W 3G (HSPA) WIRELESS ALARM COMMUNICATOR INSTALLATION MANUAL 5.0
Tabla de contenido
loading

Tabla de contenido