Returning The Refrigerant To The External Aggregate - Thermor AEROMAX SPLIT 2 Manual De Uso

Ocultar thumbs Ver también para AEROMAX SPLIT 2:
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 67
Warnings
Warranty
Use
Servicing
5.

Returning the refrigerant to the external aggregate

The external aggregate has been designed for a refrigerant volume for a refrigerant
pipe of up to 20 m.
 Switch off the heat pump and prepare the manifold and the hoses by rinsing with a
vacuum pump.
 Set the appliance to the heat pump mode (refer to "Menu service engineer"). Con-
nect the blue hose to the 3-way valve. The connected manometer should indicate low
pressure.
2-way valve
Shut the 2-way valve. The
pressure indicated by the con-
3-way valve
nected manometer begins to
drop.
Yellow hose
Once the pressure at the
manifold has dropped to ca.
1 bar, the recycling process
has been completed. Shut the
Blue hose
3-way valve.
 Remove the blue hose.
27