AUXILIARY THERMOSTAT CONFIGURATION
ACH
Kind of regulation for auxiliary relay: (Ht; CL) Ht = heating; CL = cooling.
SAA
Set Point for auxiliary relay: (-55.0 to 150.0°C; -67 to 302°F) it defines the room
temperature set point to switch auxiliary relay.
SHY
Differential for auxiliary output: (0.1 to 25.5°C; 1 to 45°F) intervention differential for
auxiliary output set point.
ACH=CL, AUX Cut in is [SAA+SHY]; AUX Cut out is SAA.
ACH=Ht, AUX Cut in is [SAA–SHY]; AUX Cut out is SAA.
ArP
Probe selection for auxiliary: (nP; P1; P2; P3; P4) nP = no probe, the auxiliary relay
is switched only by the digital input; P1 = Probe 1 (Thermostat probe); P2 = Probe 2
(evaporator probe); P3 = Probe 3 (display probe); P4 = Probe 4.
Sd
Auxiliary relay off during defrost: (n; Y) n = the auxiliary relay operates during
d
defrost. Y = the auxiliary relay is switched off during defrost.
ALARMS
ALP
Probe selection for alarm: (nP; P1; P2; P3; P4) nP = no probe, the temperature
alarms are disabled; P1 = Probe 1 (Thermostat probe); P2 = Probe 2 (evaporator
probe);
P3 = Probe 3 (display probe); P4 = Fourth probe.
ALC
Temperature alarms configuration: (Ab; rE) Ab = absolute temperature, alarm
temperature is given by the ALL or ALU values. rE = temperature alarms are referred
to the set point. Temperature alarm is enabled when the temperature exceeds the
[SET+ALU] or [SET-ALL] values.
ALU
MAXIMUM temperature alarm:
If ALC=Ab: [ALL to 150.0°C or ALL to 302°F]
If ALC=rE: [0.0 to 50.0°C or 0 to 90°F]
when this temperature is reached the alarm is enabled, after the ALd delay time.
ALL
Minimum temperature alarm:
If ALC=Ab: [-55°C to ALU; -67 to ALU]
If ALC=rE: [0.0 to 50.0°C or 0 to 90°F]
when this temperature is reached the alarm is enabled, after the ALd delay time.
AFH
Differential for temperature alarm recovery: (0.1 to 25.5°C; 1 to 45°F) intervention
differential for recovery of temperature alarm.
ALd
Temperature alarm delay: (0 to 255 min) time interval between the detection of an
alarm condition and alarm signalling.
dAo
Exclusion of temperature alarm at start-up: (0.0 to 24h00min, res. 10min) time
interval between the detection of the temperature alarm condition after instrument power
on and alarm signalling.
CONDENSER TEMPERATURE ALARM
AP2
Probe selection for temperature alarm of condenser: (nP; P1; P2; P3; P4)
nP = no probe; P1 = thermostat probe; P2 = evaporator probe; P3 = configurable probe;
P4 = Probe on Hot Key plug.
AL2
Low temperature alarm of condenser: (-55 to 150°C; -67 to 302°F) when this
temperature is reached the LA2 alarm is signalled, possibly after the Ad2 delay.
Au2
High temperature alarm of condenser: (-55 to 150°C; -67 to 302°F) when this
temperature is reached the HA2 alarm is signalled, possibly after the Ad2 delay.
AH2
AH2
Differential for temperature condenser alarm recovery: 0.1 to 25.5°C; 1 to 45°F.
Differential for temperature condenser alarm recovery: 0.1 to 25.5°C; 1 to 45°F.
Ad2
Ad2
Condenser temperature alarm delay: (0 to 255 min) time interval between the
Condenser temperature alarm delay: (0 to 255 min) time interval between the
detection of the condenser alarm condition and alarm signalling.
detection of the condenser alarm condition and alarm signalling.
dA2
dA2
Condenser temperature alarm exclusion at start up: 0.0 to 24h00min, res. 10min.
Condenser temperature alarm exclusion at start up: 0.0 to 24h00min, res. 10min.
bLL
bLL
Compressor off with low temperature alarm of condenser: (n; Y) n = compressor
Compressor off with low temperature alarm of condenser: (n; Y) n = compressor
keeps on working; Y = compressor is switched off till the alarm is present, in any case
keeps on working; Y = compressor is switched off till the alarm is present, in any case
regulation restarts after AC time at minimum.
regulation restarts after AC time at minimum.
AC2
AC2
Compressor off with high temperature alarm of condenser: (n; Y) n = compressor
Compressor off with high temperature alarm of condenser: (n; Y) n = compressor
keeps on working; Y = compressor is switched off till the alarm is present, in any case
keeps on working; Y = compressor is switched off till the alarm is present, in any case
regulation restarts after AC time at minimum.
regulation restarts after AC time at minimum.
OUTPUT RELAY
tbA
tbA
Alarm relay silencing (with oAx =ALr): (n; Y) n = silencing disabled: alarm relay stays
Alarm relay silencing (with oAx =ALr): (n; Y) n = silencing disabled: alarm relay stays
on till alarm condition lasts. Y = silencing enabled: alarm relay is switched OFF by
on till alarm condition lasts. Y = silencing enabled: alarm relay is switched OFF by
pressing a key during an alarm.
pressing a key during an alarm.
oA1
oA1
Third relay configuration (XW30LH: terminals 1-3, XW30LRH: terminals 5-6):
Third relay configuration (XW30LH: terminals 1-3, XW30LRH: terminals 5-6):
(dEF; FAn; ALr; LiG; AUS; onF; db; dEF2; HES)
(dEF; FAn; ALr; LiG; AUS; onF; db; dEF2; HES) dEF = defrost; FAn = do not select it;
ALr = alarm; LiG = light; AUS = Auxiliary relay; onF = always on with instrument on; db
= light; AUS = Auxiliary relay;
= neutral zone; dEF2 = do not select it; HES = night blind.
= do not select it;
AoP
Alarm relay polarity: (CL; oP) it set if the alarm relay is open or closed when an alarm
occurs. CL = terminals closed during an alarm; oP = terminals open during an alarm.

DIGITAL INPUTS

i1P
First digital input polarity: (oP; CL) oP = the digital input is activated by opening the
contact; CL = the digital input is activated by closing the contact.
i1F
First digital input configuration: (EAL; bAL; PAL; dor; dEF; ES; AUS; Htr; FAn;
HdF; onF; Sbt) EAL = external alarm: "EA" message is displayed; bAL = serious alarm
"CA" message is displayed; PAL = pressure switch alarm, "CA" message is displayed;
dor = door switch function; dEF = activation of a defrost cycle; ES = energy saving;
AUS = auxiliary relay activation with oA2=AUS; Htr = type of inverting action (cooling or
heating); FAn = fan; HdF = Holiday defrost (enable only with RTC); onF = to switch the
controller off; Sbt = to activate Sabbath mode.
did
Digital input 1 alarm delay: (0 to 255 min) delay between the detection of the external
alarm condition and its signalling.
When i1F= PAL, it is the interval of time to calculate the number of pressure switch
activation.
i2P
Second digital input polarity: (oP; CL) oP = the digital input is activated by opening
the contact; CL = the digital input is activated by closing the contact.
i2F
Second digital input configuration: (EAL; bAL; PAL; dor; dEF; ES; AUS; Htr; FAn;
HdF; onF; Sbt) EAL = external alarm: "EA" message is displayed; bAL = serious alarm
"CA" message is displayed; PAL = pressure switch alarm, "CA" message is displayed;
dor = door switch function; dEF = activation of a defrost cycle; ES = energy saving;
AUS = auxiliary relay activation with oA2=AUS; Htr = type of inverting action (cooling or
heating); FAn = fan; HdF = Holiday defrost (enable only with RTC); onF = to switch the
controller off; Sbt = to activate Sabbath mode.
doA
Door open alarm delay: 0 to 255 min.
1592027560 XW30LH-XW30LRH GB r1.0 14.02.2014.doc
(nP; P1; P2; P3; P4)
= configurable probe;
(-55 to 150°C; -67 to 302°F) when this
alarm is signalled, possibly after the Ad2 delay.
(-55 to 150°C; -67 to 302°F) when this
alarm is signalled, possibly after the Ad2 delay.
d2d
Digital input 2 alarm delay: (0 to 255 min) delay between the detection of the external
alarm condition and its signalling.
When i2F= PAL, it is the interval of time to calculate the number of pressure switch
activation.
nPS
Number of pressure switch activation: (0 to 15) Number of activation, during the did
or d2d interval, before signalling an alarm event (i1F, i2F=PAL).
If the nPS activation during did or d2d time is reached, switch off and on the
instrument to restart normal regulation.
odC
Compressor status when open door: (no; FAn; CPr;F_C;) no = normal;
FAn = normal; CPr = compressor OFF, F_C = compressor OFF.
rrd
Outputs restart after door open alarm: (n; Y) n = outputs follow the odC parameter.
Y = outputs restart with a door open alarm.
HES
Delta temperature during an Energy Saving cycle: (-30.0 to 30.0°C; -54 to 54°F) it
sets the increasing value of the set point [SET+HES] during the Energy Saving cycle.
CURRENT TIME AND WEEKLY HOLIDAYS (ONLY FOR MODELS WITH RTC)
Hur
Current hour: 0 to 23h.
Min
Current minute: 0 to 59min.
dAY
Current day: Sun to SAt.
Hd1
First weekly holiday: (Sun to nu) set the first day of the week which follows the holiday
times.
Hd2
Second weekly holiday: (Sun to nu) set the second day of the week which follows the
holiday times.
N.B.: Hd1, Hd2 can be set also as "nu" value (Not Used).
ENERGY SAVING TIMES (ONLY FOR MODELS WITH RTC)
ILE
ILE
Energy Saving cycle start during workdays: (0 to 23h50min) during the Energy
Energy Saving cycle start during workdays: (0 to 23h50min) during the Energy
Saving cycle the set point is increased by the value in HES so that the operation set
Saving cycle the set point is increased by the value in HES so that the operation set
point is SET+HES.
dLE
dLE
Energy Saving cycle length during workdays: (0 to 24h00min) sets the duration of
Energy Saving cycle length during workdays: (0 to 24h00min) sets the duration of
the Energy Saving cycle on workdays.
the Energy Saving cycle on workdays.
ISE
ISE
Energy Saving cycle start on holidays: 0 to 23h50min.
Energy Saving cycle start on holidays: 0 to 23h50min.
dSE
dSE
Energy Saving cycle length on holidays: 0 to 24h00min.
Energy Saving cycle length on holidays: 0 to 24h00min.
TO SET DEFROST TIMES (ONLY FOR MODELS WITH RTC)
TO SET DEFROST TIMES (ONLY FOR MODELS WITH RTC)
Ld1...Ld6
Ld1...Ld6
Workday defrost start: (0 to 23h50min) these parameters set the beginning of the 6
Workday defrost start: (0 to 23h50min) these parameters set the beginning of the 6
programmable defrost cycles during workdays. Ex: when Ld2=12.4
programmable defrost cycles during workdays. Ex: when Ld2=12.4 the second
defrost starts at 12.40 during workdays.
defrost starts at 12.40 during workdays.
Sd1...Sd
Sd1...Sd
Holiday defrost start: (0 to 23h50min) these parameters set the beginning of the 6
Holiday defrost start: (0 to 23h50min) these parameters set the beginning of the 6
6
6
programmable defrost cycles on holidays. Ex: when Sd2=3.4 the second defrost
programmable defrost cycles on holidays. Ex: when
starts at 3.40 on holidays.
starts at 3.40 on holidays.
N.B.: to disable a defrost cycle set it to "nu" (not used).
N.B.: to disable a defrost cycle set it to "nu" (not used).
OTHER
OTHER
LoC
LoC
Lock keyboard timer: nu(9) = keyboard never blocked, or 10 to 255 sec
Lock keyboard timer: nu(9) = keyboard never blocked, or 10 to 255 sec
Adr
Adr
Serial address: (1 to 247) identifies the instrument address when connected to a
Serial address: (1 to 247) identifies the instrument address when connected to a
ModBUS compatible monitoring system.
ModBUS compatible monitoring system.
PbC
PbC
PbC
Type of probe: (PtC; ntC) it allows to set the kind of probe used by the instrument:
Type of probe:
Type of probe:
PtC
PtC = PTC probe;
-
-
-
-
ntC = NTC probe.
onF
onF
On/Off key enabling:
On/Off key enabling: (nU; oFF; ES) nU = disabled; oFF = enabled; ES = not set it.
dP1
dP1
Thermostat probe display.
dP2
Evaporator probe display.
dP3
Third probe display.
dP4
Fourth probe display (only for XW30LH model).
rSE
Real set point: it shows the set point used during the energy saving cycle or during the
continuous cycle.
rEL
Software release for internal use.
Ptb
Parameter table code: readable only.
9. DIGITAL INPUTS
The first digital input (XW30LH: terminals 13-14; XW30LRH: terminals 14-15) is enabled if P3P=n.
With P3P=n and i1F=i2F the second digital input will be disabled.
The free voltage digital inputs are programmable by the i1F and i2F parameters.
9.1 GENERIC ALARM (i1F or i2F = EAL)
As soon as the digital input is activated the unit will wait for did time delay before signalling the "EAL"
alarm message. The outputs status doesn't change. The alarm stops just after the digital input is de-
activated.
9.2 SERIOUS ALARM MODE (i1F or i2F = bAL)
When the digital input is activated, the unit will wait for did delay before signalling the "CA" alarm
message. The relay outputs are switched OFF. The alarm will stop as soon as the digital input is de-
activated.
9.3 PRESSURE SWITCH (i1F or i2F = PAL)
If during the interval time set by did parameter, the pressure switch has reached the number of
activation of the nPS parameter; the "CA" pressure alarm message will be displayed. The compressor
and the regulation are stopped. When the digital input is ON the compressor is always OFF. If the
nPS activation in the did time is reached, switch off and on the instrument to restart normal
regulation.
9.4 DOOR SWITCH INPUT (i1F or i2F = dor)
It signals the door status and the corresponding relay output status through the odC parameter: no:
normal (any change); FAn: Fan OFF; CPr: Compressor OFF; F_C: Compressor and fan OFF.
Since the door is opened, after the delay time set through parameter did, the door alarm is enabled,
the display shows the message "dA" and the regulation restarts if rtr=YES. The alarm stops as
soon as the external digital input is disabled again. With the door open, the high and low temperature
alarms are disabled.
XW30LH – XW30LRH
3/5