EXAMPLE 2 (2MBHZ...models)
1. Expansion joint/anti-vibration mount
2. Upstream ball valve
3. RG/2MBHZ... pressure regulator
4. Ball valve downstream of the regulator
1
2
4.0 - MANUAL RESET
• Make sure that all valves and downstream cocks are closed;
• Unscrew the cap (10);
• Lightly press the reset pin (18), wait a few moments for the pressure to balance and then the reset pin (18) to stroke end;
• While holding down the reset pin (18), slowly open the cock downstream of the regulator;
• Release the reset pin (18);
• After that tighten the cap (10) back in the initial position.
5.0 - COMMISSIONING
Before commissioning, ensure that:
• all of the indications on the rating plate, including the direction of flow, are complied with;
• the holes of the dust caps (13) and (25) are not clogged (regulator and shut-off);
• IMPORTANT: Use appropriate manual gas shutoff devices to avoid damaging the regulator;
• The equipment pressurising operation must be carried out very slowly so as to prevent possible damage. To seal
the downstream section of the pipe:
• feed the regulator with the inlet pressure;
• slowly close the ball valve downstream of the regulator:
• while ensuring that the relief valve and any safety shut-offs are not triggered, check that the pressure
(indicated on the pressure gauge) remains stable (does not drop).
NOTE: under no circumstances should a blind cap be installed in place of the dust caps (13) and (25) as the
regulator and/or the safety shut offs might not work;
• Close the ball valve downstream of the regulator and partially open the downstream relief valve;
• Slowly open the upstream shut-off devices;
• Close the vent valve;
• Manually reset the regulator (see 4.0);
RG/2MCSH - RG/2MBHZ
5. Vent valve
6. Relief valve MVS/1
7. Low pressure gauge and relevant button
8. High pressure gauge and relevant button
discharge in
open air
8
3
Obligatory
shut off connection
for DN 65-80-100
16
6
7
Ø ext. min 8mm
Ø int. min 6mm
Madas Technical Manual - 5|5.3b - REV. 0 of 2
discharge in
open air
5
4
Sep 2019