Control Terminals - BONFIGLIOLI Vectron AEC Guia De Inicio Rapido

Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

4.3

Control terminals

CAUTION
Power supply must be turned off before connecting control inputs and outputs.
Non-observance may damage the device.
X210A
24 V
ext.
X210B
-
+
-
+
V
Term.
1 ... 3 Relay output, floating change-over contact, response time approx. 40 ms,
maximum contact load:
make contact:
break contact:
Digital inputs (X210A.3 ... X210B.2): Low signal: DC 0 V ... 3 V, High signal: DC 12 V ... 30 V,
Input resistance: 2,3 kΩ, response time: 2 ms (S1IND and S7IND: 10 ms), PLC compatible
Digital output (X210B.3): Low signal: DC 0 V ... 3 V, High signal: DC 12 V ... 30 V,
maximum output current: 50 mA, PLC compatible
Multifunction output (X210B.4):
Analog signal: DC 19 ... 28 V, maximum output current: 50 mA, pulse-width modulated signal (f
Digital signal: Low signal: DC 0 V ... 3 V, High signal: DC 12 V ... 30 V, maximum output current: 50 mA,
PLC compatible,
Frequency signal: Output voltage: DC 0 V ... 24 V, maximum output current: 40 mA,
maximum output frequency: 150 kHz
Multifunction input (X210B.6):
Analog signal: input voltage: DC 0 V ... 10 V (R
Digital signal: Low signal: DC 0 V ... 3 V, High signal: DC 12 V...30 V, response time: 4 ms, PLC compatible
Conductor cross-section:
The signal terminals are suitable for the following cable sizes:
with ferrule:
0.25...1.0 mm²
without ferrule: 0.14...1.5 mm²
06/13
+20 V/180 mA
1
X210A.1
2
GND 20 V
3
S1IND
4
S2IND
X210A.2
5
S3IND
X210A.3
6
S4IND
X210A.4
7
S5IND
X210A.5
X210A.6
X210A.7
1
S6IND
2
S7IND
3
S1OUT
X210B.1
4
MFO1A
X210B.2
+10 V/ 4 mA
5
X210B.3
6
MFI1A
7
GND 10 V
X210B.4
X210B.5
X210B.6
X210B.7
Control terminal X10
Description
AC 5 A / 240 V, DC 5 A (ohmic) / 24 V
AC 3 A / 240 V, DC 1 A (ohmic) / 24 V
Technical data of control terminals
=70 kΩ), input current: DC 0 mA ... 20 mA (R
i
Quick Start Guide AEC
Control terminal X210A
Voltage output DC +20 V or input
for external power supply DC 24 V
±10%
GND 20 V/ GND 24 V (ext.)
S1IND
Mains unit release
S2IND
Digital input
S3IND
Digital input
S4IND
Digital input
S5IND
Digital input
Control terminal X210B
S6IND
Digital input
S7IND
Mains unit release
S1OUT
Digital output (default
setting: "No fault"
message)
MFO1A
Multifunction output
MFI1A
Voltage output DC +10 V
Multifunction input
GND 10 V (earth)
GB
= 116 Hz),
PWM
=500 Ω),
i
37
Tabla de contenido
loading

Tabla de contenido