ENGLISH
Menu's
Entrance to menu's (see fig. 10)
From Home Image the status menu can be
reached by one push on
. From Home
Image the Setup & service menu can be
reached by one push and hold on
For entrance a Log in is required by the
password given during commisioning.
Parameter mode (read/write mode)
When maneuvering in Setup & service
menu or Status menu there is an overall
logic of showing possible actions for each
parameter.
Plain text:
Read only
Framed text:
Parameter can be changed - push
highlight.
Highlighted text:
Scroll with
/
to the desired selection
and push
to enter the selection.
Once entered the parameter is valid and
the text changes to framed text.
© Danfoss A/S (DF), 2016-01
Status menu
To enter Status menu from Home image:
Push
once.
.
The Status menu is an open menu acces-
sible for all. Therefore only 1 parameter
can be changed from here. A selection of
other parameters can be seen from the
status menu:
Status menu ( Open menu )
Setpoint
Liquid level setpoint
Active alarms
Example of alarm content. The list will be empty in
normal operation as no alarm is active.
Level signal out of range
Standby mode
Detailed status
Controller state
to
Actual level
Actual reference
Actual OD
Digital input status
Actual level signal current
Oscillation amplitude
Oscillation period
Controller Info
Type
Name (Controller name)
SW (Software version)
Bios (Bios version)
Adr (Controller address)
SN (Serial Number)
PV (Product version)
Site (Production site)
QR code
Code
Read & Write
Read only
DKRCI.PI.RP0.C3.ML / 520H8794
Setup & service menu
(Requires log-in password assigned in
Commisioning menu)
Options
To enter Setup and service menu from
0 - 100%
Home image:
Push and hold
Maneuvering in the Status menu and the
hours
minutes
Setup and service menu's are done by use
hours
minutes
of the 4 push buttons shown in fig. 8.
Stop, Manual, Auto,
Slave, IO
The Setup & service menu is divided into
0.0 - 100%
3 access levels, where personnel have
0.0 - 100%
individual authority.
0.0 - 100%
On / Off
Most advanced level is Commissioning,
mA
where you have access to change all
0.0 - 100%
allowable parameters, including password
sec
issuing and re-run of Setup wizard. Default
password for commissioning is 300.
Service level is for service personnel and
has fewer rights than commissioning.
Default password is 200.
The lowest level is for Daily use, and allows
only a few changes. Default password is
100.
Below table shows authority given to the
3 levels.
.
7