Configuration
Caution
The CPV Direct contains electronically sensitive compo-
nents. The CPV Ddirect will be damaged if you touch
the contact surfaces of the plug connectors and if you
do not observe the regulations for handling electro-
statically sensitive components.
Proceed as follows when configuring:
1. Switch off the power supply.
2. Remove the switch module.
3. Set the following with the DIL switches: baud rate,
extension to the CP system, station number.
4. Refit the switch module.
5. If the CP system is the first or last slave in a field bus
segment, a terminating resistor must be fitted
between the field bus cables (120
Warning
S Make sure that switch-on test pulses are sup-
pressed/switched off when you operate the CPV
Direct via a "safety I/O module".
S Check the measures required for putting your system
into a safe status in the event of an EMERGENCY
STOP.
Further information can be found in manual
P.BE-CP-CO2-.. .
Festo CPV..-GE-CO2-8 0107NH English
9
, 0.25 W).
17