4.2
Internal lay-out
The Control panel has the following elements:
E
Sensors
Zones
Z4 Z3 Z2 Z1
USB
A. Power supply connector.
Located in the bottom of the box in the right place. It is for connecting electrical power supply
(Neutral, Earth and Line). The power line must be connected through the terminal which has
the fuse, and the ground one, through the centre.
B. Switching power supply
Circuit protected by a shield located at the bottom of the box in the top center place. It is
connected to the power supply connector and the outputs card. Its function is to adapt the
supply voltage required by the other circuits.
C. Output card
Circuit with the battery connection, ventilation, alarms, etc, for 1 or 2 Zones. In control panels
of 2 zones, it is located in the bottom of the box on the left central region (C1 in Figure 5). In
control panels of 3 or 4 zones, it has a second output card on the right central area (C2 in
Figure 5). Output card left C1 is connected to the switching power supply. Additionally, if the
control panel has 2 output cards (C1 and C2), these are also connected to each other.
WARNING:
In order to manoeuvre the Label holder, care must be taken with the ground cable
connecting one of its pin with the Switching circuit faston, and the connector of the
CPU with the output circuit (-SEE WARNING CHAPTER 11 -).
D. Batteries
The control panel has space to place 2 batteries 12 Vdc 7Ah if necessary (DVB models).
They are at the bottom of the box in the bottom center and right side.
E. CPU card
It is located in the rear of the label holder protected by a shield. At the bottom there are the
connectors for zones and USB type B.
WARNING:
In order to manoeuvre the Label holder, care must be taken with the ground cable
connecting one of its pin with the Switching circuit faston, and the connector of the
CPU with the output circuit (-SEE WARNING CHAPTER 11-).
32
Ctra. de Molins de Rei a Rubí, Km. 8,4 - 08191 RUBÍ (Barcelona) ESPAÑA.
Addressable Control Panel for CO and NO
ZafirCO
C1
Zone 1
Figure 5: Internal lay-out