Parameter
Ventilation level 1
Delay to activation of ventilation 1
Delay to stop of ventilation 1
Ventilation level 2
Delay to activation of ventilation 2
Delay to stop of ventilation 2
Alarm level
Delay of activation of alarm
Delay to stop of alarm
Average concentration
If the concentration of toxic gas in that zone falls below the concentration level of ventilation 1,
ventilation of the zone will stop only after the lapse of the delay time to stop of ventilation 1.
By contrast (only DVB models), if the concentration in that zone continues to increase,
ventilation 2 zone will be activated only after be above this level more than the delay time to
activation of ventilation 2.
Ctra. de Molins de Rei a Rubí, Km. 8,4 - 08191 RUBÍ (Barcelona) ESPAÑA.
Tlf.: +34 935 862 690 - Fax:+34 936 999 261 - [email protected] - www.cofem.com
Addressable Control Panel for CO and NO
Figure 2: Operation scheme of DVB control panels
50 ppm CO
1 ppm NO
2
4 min
4 min
100 ppm CO
3 ppm NO
2
4 min
4 min
200 ppm CO
5 ppm NO
2
1 min
1 min
0 min (instantaneous)
Figure 3: Configurable parameters
FIRE PROTECTION MANUFACTURER
ZafirCO
Value
5-300 ppm (CO)
0,1-20 ppm (NO
0 - 10 min
0 - 10 min
Nivel Vent. 1 - 300 ppm (CO)
Nivel Vent. 1 - 20 pm (NO
0 - 10 min
0 - 10 min
Nivel Vent. 2 - 300 ppm (CO)
Nivel Vent. 2 - 20 ppm (NO
0 - 5 min
0 - 5 min
0 - 60 min
2
Margin
)
2
)
2
)
2