Connecting wired accessories
Zone 1, Zone 2, Zone 3 and Zone 4 are the EOLR wired zones that support
devices (sensors) with NO (open circuit) and NC (closed circuit) signal with
a response time of 300 ms. Maximum resistance of the area: 11000 Ohms +
EOLR
Connect the NC (Normally Closed) devices in series at the top of the loop. The
EOLR resistor must be connected in series with the devices to the last device.
Connect the NO (open circuit) devices in parallel, in the loop.