Chapter 7: Maintenance; Chapter 8: Technical Data - AKO -52201 Manual Del Usuario

Alarma de detección de fugas de gases para conexión permanente
Ocultar thumbs Ver también para AKO-52201:
Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

Detector heating time
After receiving the electrical power supply, the gas detector needs a heating time of around 5 minutes,
during which it will NOT detect leaks. This time is indicated by means of a quick flashing of the green led
on the detector itself.
Self-diagnosis function
The unit incorporates a self-diagnosis system of the detector and the wiring between the detector and alarm station.
In the case of malfunction, the station will alert making three consecutive tones every 2 minutes, and activating the
visual alarm and the detector status led, while the detector will alternately activate its status leds.
7.- Maintenance
Clean the surface of the equipment with a soft cloth, water and soap.
Ÿ
Do not use abrasive detergents, petrol, alcohol or solvents, as this might damage the sensor.
Ÿ
AKO guarantees the correct operation of the detectors during the first 3 years from the date of purchase,
Ÿ
and after this time, it is advisable to replace the detector.
We recommend changing the detector in the event of having been exposed to high gas concentrations.
Ÿ
The correct operation of the detector should be checked at least once a year, ask about if
your current local regulations require lower intervals.
This check consists of exposing the detector to a small gas concentration and check that
all the relay indications and outputs work correctly.
8.- Technical data
AKO-52210
Power supply ........................................................................................................................90-260 V~ 50/60 Hz
Maximum input power ................................................................................................................................10 VA
No. of inputs.......................................................................................................................................................1
Compatibility of inputs ......................................................................................Only AKO-52211/52212 detectors
Alarm / pre-alarm relay ...........................................................................................SPDT 230 Vac, 16 A, cos j =1
Working ambient temperature ..........................................................................................................0 ºC to 50 ºC
Storage ambient temperature ........................................................................................................-30 ºC to 70 ºC
Protection degree .........................................................................................................................................IP 40
Installation category ....................................................................................................................II s/ EN 61010-1
Pollution degree ..........................................................................................................................II s/ EN 61010-1
Double isolation between power supply, secondary circuit and relay output.
Sound power..........................................................................................................................90 dB(A) at 1 metre
EMC Standard.......................................................................................................................................EN 61000
AKO-52211/52212
Power supply..................................................................................................................................15 Vdc ±3 Vdc
Consumption Typical................................................................................................................................75 mA
Maximum.........................................................................................................................100 mA
Working ambient temperature .......................................................................................................-20 ºC to 50 ºC
Storage ambient temperature ........................................................................................................-20 ºC to 60 ºC
Range of maximum allowed humidity .............................................................5 - 85% RH (without condensation)
Protection degree .........................................................................................................................................IP 40
Life...................................................................................Depending on the temperature and humidity conditions
EMC Standard.......................................................................................................................................EN 61000
13

Capítulos

Tabla de contenido
loading

Este manual también es adecuado para:

Ako-52202Ako-52210Ako-52211Ako-5221252201

Tabla de contenido