Please note
To comply with protection class IP65/IP67:
S Seal unused CP connections and the Save key with
the appropriate protective caps.
3.3 Saving the string assignment
1. Switch on the power supply of the CPX terminal and, if
necessary, of the CP modules using the load voltage
connection.
2. Use a small screwdriver or similar to press the Save
key for at least 1 s.
This will save the current string allocation as the set
string allocation in the CPX−CP interface. The corre
sponding I/O addresses are assigned to the CP mod
ules.
3. Check whether the status LEDs on the modules light
up and the string LEDs (L1 ... L4) on the CPX−CP inter
face have gone out. If this is the case, all the CP mod
ules are ready to operate and the saved string assign
ment is identical to the current string assignment.
4. Switch the power supply of the CPX terminal off and
back on.
5. Depending on field bus node or FEC being used, the
modified address range of the CPX−CP interface must
be accepted:
Festo CPX−CP−4−FB xxxxNH English
15