LIEBERT® GXT5™ UPS 208-V GXT5-6KL630RT5UXLN
Quick Installation Guide
GXT5
UPS to External Battery Cabinet Connections
TM
Single/First EBC
Second EBC
CONNECTIONS
4. Connecting External
Battery Cabinet
(Optional)
External battery cabinets
(EBC)provide longer battery
run-time for connected
devices. Refer to GXT5 User
Guide, to select the appropriate
model and quantity for your
GXT5 model and applications.
• Verify that the EBC breaker
is in the "Off " position.
• Connect one end of the
supplied EBC cable to the
UPS and one end to the
battery cabinet. If connecting
more than one external
battery, connect one end of
the external battery cable to
the second connector on the
battery cabinet, then connect
the other end to the next
battery cabinet.
5. Connecting the UPS
to Receptacle
The UPS is cord and plug
connected using a L6-30P
2
590-1930-665A/SL-70306_REV0
UPS rear panel
input plug. Perform all wiring in
accordance to all local and
national electrical codes. The
UPS is equipped with output
receptacles. Connect the
equipment to be protected to
the output receptacles.
NOTE: Allow the batteries to
charge at-least 8 hours before fi rst
start-up to ensure adequate
back-up time. The batteries charge
when the UPS is connected to AC
input regardles of the off /on status
of the UPS.
POWERING THE UPS
NOTE: Do not start the UPS until
after the installation is fi nished, the
system is commissioned by an
authorized engineer, and the
external input circuit breakers are
closed.
1. Make sure the maintenance
bypass switch is in the open
"OFF" position and that the
guard is secured in place.
2. Ensure that the REPO
connector on the rear of the
EBC terminal
Operation and Display Panel
Display screen
Power
Run
Alarm
Up
Enter
Escape
Down