UNIT ADJUSTMENT - PUSH N' LEARN (PNL)
Load Selection Procedure
A configuration button (Config) allows access to WattStopper's
patented Push n' Learn™ technology to change binding
relationships between sensors, switches and loads.
NOTE: Unlike the LMRC and LMPL products, the installation
of the LMFC inside of a fixture means that though this
method is supported, it is primarily suited to assembly line
verification. Field verification should be done using LMCS
software whenever possible to avoid fixture disassembly.
To avoid accidental actuation, the buttons are recessed
below the housing surface. Use a tool such as a precision
screwdriver or ballpoint pen to access Push n' Learn
functionality.
Step 1 Enter Push n' Learn
1. Press and hold the Config button (on any DLM device) for 3 seconds. (On the LMFC-011, use a pointed tool.)
2. The red LED on the LMFC-011 begins to blink. When you release the button, the red LEDs on other communicating devices
connected to the DLM Local Network begin to blink. They continue to blink until you exit PnL mode.
3. All loads in the room turn OFF immediately after entering PnL, then one load will turn ON. This is Load #1, which is bound to
switch button #1 and occupancy sensors as part of the Plug n' Go factory default setting. All switch buttons and sensors that
are bound to this load have their blue LED solid ON.
Step 2 Load selection
1. Press and release the Config button to step through the loads connected to the DLM Local Network. As each load turns ON note
the devices (switch buttons and sensors) that are showing a bright solid blue LED. These devices are currently bound to the load
that is ON. The blue LED on the room controller or plug load controller connected to the load is also lit.
• To unbind a switch or dimmer button from a load, press the switch button while its blue LED is ON bright. The blue LED goes
dim to indicate the button no longer controls the load that is currently ON.
• To unbind an occupancy sensor, press the up () or down () adjustment button while its blue LED is ON. The blue LED turns
OFF to indicate the sensor no longer controls the load that is currently ON.
• Pressing the switch button or sensor up () or down () again while the load is ON rebinds the load to the button or sensor
and the blue LED illuminates brightly.
Step 3 Exit Push n' Learn
Press and hold the Config button until the red LED turns OFF, approximately 3 seconds.
LEDs turn ON and OFF
but load doesn't switch
Lamps do not dim, or
lamps drop out at low
dim levels
TROUBLESHOOTING
1. Make sure the DLM local network is not in PnL.
2. Check load connections to fixture controller.
1. Make sure a 0-10V dimming ballast and rapid start sockets are installed per the ballast
manufacturer's recommendation. Shunted sockets are typically not acceptable.
2. Check wiring per ballast manufacturer's instructions.
DLM Local Network – 24V (RED)
DLM Local Network – GND (BLACK)
DLM Local Network – COM (BLUE)
Blue LED ON when
load is ON.
Load button:
Press & release for
ON/OFF.
Press & hold to Dim.
3
DIM+ (VIOLET)
DIM+ (VIOLET)
DIM− (GRAY)
DIM− (GRAY)
BLUE
LOAD
CONFIG
RED