LEGRAND LMRC-213 Guia De Inicio Rapido

LEGRAND LMRC-213 Guia De Inicio Rapido

Relé triple dlm con controlador de regulación de habitación de 0 a 10 v
Idiomas disponibles

Idiomas disponibles

Enlaces rápidos

No: 23994 – 11/16 rev. 1
Catalog Numbers • Les Numéros de Catalogue • Números de Catálogo: LMRC-213/LMRC-213-347
Country of Origin: Made in China • Pays d'origine: Fabriqué en Chine • País de origen: Hecho en China
LMRC-213-U and LMRC-213-347 -U are BAA and TAA compliant (Product produced in the U.S.)
This unit is pre-set for Plug n' Go™ operation, adjustment is
optional.
For full operational details, adjustment and more features of the
product, see the DLM System Installation Guide provided with
Wattstopper room controllers, and also available at
www.legrand.us/Wattstopper.
Installation shall be in accordance with all applicable regulations,
local and NEC codes. Wire connections shall be rated suitable for
the wire size (lead and building wiring) employed.
For Class 2 DLM devices and device wiring: To be connected to a
Class 2 power source only. Do not reclassify and install as Class 1, or
Power and Lighting Wiring.
PLACEMENT EXAMPLE
Daylighting
LMRC-21x
Sensor
Room
Controller
CAUTION: TO CONNECT A COMPUTER TO THE DLM LOCAL NETWORK USE THE
LMCI-100. NEVER CONNECT THE DLM LOCAL NETWORK TO AN ETHERNET
PORT – IT MAY DAMAGE COMPUTERS AND OTHER CONNECTED EQUIPMENT.
Wattstopper
DLM Triple Relay w/0-10V Dimming Room Controller
DLM relais triple avec contrôleur de pièce de gradation 0-10 V
Relé triple DLM con controlador de regulación de habitación de 0 a 10 V
Quick Start Guide • Guide de démarrage rapide • Guía de inicio rápido
Voltage
LMRC-213 Input Voltage ................... 120/277VAC, 50/60Hz
LMRC-213-347 Input Voltage................... 347VAC, 50/60Hz
Load Requirements
LMRC-213 ........................................Not to exceed 20A total
LMRC-213-347 .................................Not to exceed 15A total
Class 2 Dimming Output, 0-10V .......sinks up to 100mA per channel
Output to DLM Local Network ................. up to 250mA @ 24VDC
Connection to the DLM Local Network .................... 4 RJ-45 ports
DLM Local Network characteristics when using LMRC-11x/2xx
room controllers:
Low voltage power provided over Cat 5e cable (LMRJ);
max current 800mA. Supports up to 64 load addresses,
48 communicating devices including up to 4 LMRC-10x
series and/or LMPL-101 controllers.
Free topology up to 1,000' max.
Environment ................................................. For Indoor Use Only
Operating Temperature .................32° to 131°F (0° to 55°C)
Storage Temperature ...................23° to 176°F (-5° to 80°C)
Relative Humidity .......................5 to 95% (non condensing)
Patent Pending
Corner Mount
Occupancy
Sensor
J Box
To
Load
Ceiling Mount
To 0-10V
Occupancy
Dimming Ballast
®
SPECIFICATIONS
Each relay rated for up to:
Incandescent. .......................................20A @ 120VAC
Ballast ...........................................20A @ 120/277VAC
Motor ................................................... 1Hp @ 120VAC
Each relay rated for up to:
Ballast/LED Driver ................................15A @ 347VAC
DLM Local Network
(low voltage, Class 2)
LMRJ cables
Switch/
Sensor
Dimmer
loading

Resumen de contenidos para LEGRAND LMRC-213

  • Página 7: Especificaciones

    DLM con un receptáculo RJ45 abierto. Todo el cableado de voltaje de línea es #12 AWG. Para el LMRC-213, cada relé está calificado para hasta 20 A; la carga total del LMRC-213 no debe exceder 20 A. Para el LMRC-213-347, cada relé está calificado para hasta 15 A; la carga total del LMRC-213-347 no debe exceder 15 A.
  • Página 8 LMRC-213 tiene dos relés de carga. En una red local DLM con solamente controladores de habitación LMRC-213, el dispositivo LMRC-213 con el número de serie más alto será el Maestro, y tendrá la cargas 1, 2, y 3. El siguiente número de serie mayor tendrá la cargas 4, 5, y 6, y así...
  • Página 9: Solución De Problemas

    Todas las cargas de la habitación se desactivarán de inmediato después de entrar a PnL; a continuación, se activará una carga. Esta es la carga N.° 1, que está vinculada con el botón interruptor N.°1 y con los sensores de ocupación, según la configuración predeterminada de fábrica de Plug n’...
  • Página 12 No. 23994 – 11/16 rev. 1 © Copyright 2016 Legrand All Rights Reserved. 800.879.8585 © Copyright 2016 Tous droits réservés Legrand. www.legrand.us/wattstopper © Copyright 2016 Legrand Todos los derechos reservados.

Este manual también es adecuado para:

Lmrc-213-347Wattstopper lmrc-213Wattstopper lmrc-213-347