For connection between the modules, use twisted pair cable (ex. EIB 2x2x0.8mm2, UTP 8x0.51mm - CAT5 or other).
Use minimum 0.5mm² cable. For long wiring (>50m) or if a lot of modules ( > 10) are connected to one wire, use 1mm² cable.
Connect the 12-18Vdc (mind the polarity) and connect the bus wires (mind the polarity).
REACTION TIME
The push buttons have a default short reaction time (65ms). There is possibility to maintain the push button pressed for 1, 2 or 3 seconds
until they are considered as being closed.
Follow this procedure:
1. Set the hexadecimal rotary switches on one off following positions:
2. Press now (min. 3 seconds) every push button you would like to assign this reaction time to.
In this mode the connected LEDs parallel to the push buttons will turn on in different ways to
indicate the chosen reaction time:
Very fast blinking: 65ms
Fast blinking: 1 second
Slow blinking: 2 seconds
Continuous: 3 seconds
These reaction times are saved into the module (even in case of a power failure).
3. Exit the mode by resetting the address at the original value.
ENGLISH
Address
Reaction time
F0
65ms
F1
1 second
F2
2 seconds
F3
3 seconds
3