Modo de trabajo
WorkMode
Auto Test
Modo de trabajo
WorkMode
YES ?
SI?
Press "enter"more
Presione "Enter" más
than 3 seconds to enter
de 3 segundos para entrar
59.S2
Limit
Waiting to start
Esperando para iniciar
59.S2
Limit
264.5 V 200ms
59.S2
Testing
230.8 V - xxx V
59.S2 Pass
264.7 V
180ms
27.S1
Limit
195.5 V 400ms
59.S2
Testing
230.8 V - xxx V
59.S2 Pass
194.7 V
380ms
81>S2
Limit
51.5HZ 100ms
81>S2
Testing
50.01-xxxxHz
81>S2 Pass
51.52HZ
80ms
81<S2
Limit
47.50HZ 100ms
81<S2
Testing
50.01-xxxxHz
81<S2 Pass
47.49HZ
80ms
Page 70/70
59.S1
Limit
253.0V 3000ms
59.S1 Testing
230.4- xxxxV
59.S1 Pass
254.7V 3000ms
27.S2
Limit
92.0V 200ms
27.S2 Testing
230.4- xxxxV
27.S2 Pass
90.8V 180ms
81>S1
Limit
50.5HZ 100ms
81>S1 Testing
50.01- xxxxHZ
81>S1 Pass
50.05V 80ms
81<S1
Limit
49.5HZ 100ms
81<S1 Testing
50.01- xxxxHZ
81<S1 Pass
49.5HZ 80ms
Auto Testing
Auto Test Passed