Fan motors and electric defrost heater connection scheme and absorption data (L4 models)
Model with ø 200 mm fan motors
M = fan motor
R = defrost heater
L1 = brown
N1 = blue
L2-N2 = black
= green/yellow
L1-N1 = 230V/1/50-60Hz fan motor electric feed line
L2-N2 = 230V/1/50-60Hz electric heater feed line
Important
The motors are equipped with inner thermal protection with automatic
reconnection.
Before using motor speed control systems verify the compatibility with the
motors.
Non compatible systems may damage motors or increase noise level; the
manufacturer will not be responsible for model performance with speed con-
trol systems.
CGS Model ø 200 mm
Fan motors
n° x Ø mm
Fan motors
A
absorption
W
Heater absorption
W
11EH3
11AH3
12EH3
11EL4
11AL4
12EL4
1x200
1x200
2x200
0,35
0,35
0,7
53
53
106
480
480
650
Important
Application of adequate thermal control systems on feeder lines is manda-
tory.
Performance of the electric heater must be periodically controlled to avoid
damage due to ice build-up.
The manufacturer is not liable in any way for defects caused by non detec-
ted malfunctions.
12AH3
12LH3
12MH3
12AL4
12LL4
12ML4
2x200
2x200
2x200
0,7
0,7
0,7
106
106
106
680
680
850
230V/1/50Hz Feed
13EH3
13AH3
13MH3
13EL4
13AL4
13ML4
3x200
3x200
3x200
1,05
1,05
1,05
159
159
159
1080
1200
1200
www modine com
14MH3
14ML4
4x200
1,4
212
1600
25