Take into account general and specifi c local regulations. Unit must be dis-
connected from any power source when any task is done over it. Qualifi ed
personnel must only carry out all actions described and mentioned. After
EN
electrical connection, carefully check all terminals and carry out an initial
test. Check correct FU fuses work from control unit.
The COR-PRO-V air curtains are equipped with an operating ther-
mostat with automatic reset (located in each electrical resistance)
and an emergency thermostat with manual reset. If the tempera-
ture limit inside the unit is exceeded, the emergency thermostat
(Pop-up button) turns off the heating circuit. The button is used to
unlock the safety thermostat in case of equipment failure. Once
the air curtain has cooled down, press the emergency thermostat
button to the starting position.
ATTENTION: Unlocking the emergency thermostat does not solve any problem on the device. It is a warning
element that point something is not working correctly
9. COMMISSIONING
Before commissioning the unit, carry out following verifi cations:
• External casing integrity
• Ceiling or wall anchoring mounting
• Easy and direct access to inspection and maintenance door
• Supply voltage main presence
• Cables properly attached to their terminals
• Absence of mechanical objects or residues in inlet / outlet sides
10. REMOTE CONTROL OPERATION (Ditronic)
Remote control device is a touch screen type, for wall installation and it comes from factory with all
COR-PRO V models as default (on demand, special SM version without remote control for air curtain unit
working as Slave). In addition, remote control packaging includes an Ambient/room temperature sensor that
can be installed on the wall voluntarily if working in automatic mode, this room sensor is selected instead of
discharge air temperature sensor (installed inside air curtain by default).
Remote control requires RJ45 cable between control device and air curtain (not included). The RJ45-10 COR-PRO acces-
sory is offered as an option with a fi xed length of 10m. In case of Master-Slave connection between two air curtains, cable
required is RJ11 type (not included). The RJ 11-5 COR-PRO accessory is offered as an option with a fi xed distance of 5m.
20
Control Unit – Terminal connections