13. MAPA MODBUS / MODBUS MAP / CARTE MODBUS
Input registers (Read)
Register
HEX
DEC
0FFFh
4095
Current room temperature
1000h
4096
Current outlet temperature
1001h
4097
Current media temperature
1002h
4098
Motor type
1003h
4099
Door contact status
1004h
4100
Fan status
1005h
4101
BIT error array
1006h
4102
Outdoor sensor temp.
1007h
4103
Temperature setpoint
1008h
4104
Controller status
1009h
4105
Control device version
38
Discrete input
Data type
Range
Default
16bits
0-255
16bits
0-255
16bits
0-255
BIT
0-1
BIT
0-1
16bits
0-3
b6: Outdoor temp. Sensor error
b5: Slave curtain error
b4: Anti-frost protection active
-
-
b3: Door curtain communication error
b2: Outlet sensor error
b1: Room sensor error
b0: Motor error
16bits
-127 – 128
16bits
0-255
b7: Electric version
b6: Door contact active
b5: Outdoor temp. sensor active
-
-
b4: Weekly timer active
b3: Heating active
b1: Panel ON
16bits
0-255
Comments
0 0°C
1 0,5°C
...
-
100 50°C
101 51,5°C
...
0 0°C
1 0,5°C
...
-
100 50°C
101 51,5°C
...
0 0°C
1 0,5°C
...
-
100 50°C
101 51,5°C
...
0 AC version
0
1 EC version
0 Door opened
-
1 Door closed
0 Fan off
1 Speed 1
-
2 Speed 2
3 Speed 3
-127 -63,5°C
-126 -63°C
...
-1 -0,5°C
0 0°C
—
1 0,5°C
...
128 99°C
129 99,5°C
0 0°C
1 0,5°C
...
-
100 50°C
101 51,5°C
...
123
1.23 version