3.
Profibus Module Connection and Configuration
3.1
Adjustment
Figure 3-1 Adjustment switches
Before powering up the Profibus Module, set the two rotary switches so that the module
address matches the address set in your Master configuration tool (the diagram shows
the factory default setting for the rotary switches).
The module automatically detects the network data rate.
3.2
Connection
The module connects to the Profibus network via a standard 9 pin Sub-D connector.
The Profibus Module can be powered through the network cable or externally (24 Vdc).
Figure 3-2 Profibus Module connections
Digistart CS
3
Digistart CS
Profibus Module
External 24 Vdc supply required if not powered through
bus
9-pin Sub-D connector to Profibus network
Pin No.
1
Shield
2
24 Vdc negative (optional)
3
RxD/TxD-P
4
not used
5
DGND
6
VP (end of bus slave only)
7
24 Vdc positive (optional)
8
RxD/TxD/-N
9
DGND
Profibus Module User Guide
Issue 1
1
2
4
9 pin Sub-D connector
www.controltechniques.com
MSD
LSD
Digistart IS
3
Digistart IS (Remote mode)
DI2, +24V: Stop
DI3, +24V: Reset
Profibus Module
External 24 Vdc supply required if not powered through
bus
9-pin Sub-D connector to Profibus network
Assignment
ADDRESS
1
2
4
5