After having installed the appliance, check for any leaks in the
fittings. While looking for leaks, we recommend using non-corrosive
When checking for leaks do not use naked flames!
The manufacturer shall not be held responsible and the guarantee is void in case of damage caused by negligence in following
the operating and installation instructions or by improper use. The guarantee is void in case of connections that don't meet the
current standards and fire-fighting regulations.
This equipment doesn't need to be connected to a flue, but we do recommend installing it under an extractor hood.
The distribution network pressure must meet the following
specifications:
ALLOWED
LPG
NOT ALLOWED
ALLOWED
METHANE
H
NOT ALLOWED
If the gas distribution network pressure on the installation site doesn't
meet the above values, inform the gas board and do not turn the unit
on until the reason has been found and eliminated.
The manufacturer refuses all responsibility in case of damages caused by wrong installation, inaccurate maintenance and
inobservance of the safety regulations.
Evacuation of burnt gases
Checking the pressure
From 20/25 to 35/45 mbar
Below 20/25 above 35/40 mbar
From 17 to 25 mbar
Below 17 above 25 mbar
foam products, such as leak detection sprays.
The distribution network pressure can be taken with a U manometer
(min. definition 0.1 mbar), connected to the pressure outlet behind
the control panel "H" (pic.2).
1.
Remove the control panel.
2.
Remove the screw and the washer (pic.2) from the pressure
outlet and connect the manometer.
3.
Turn the unit on following the enclosed instructions and check
that the pressure is within the permitted pressure range.
4.
Disconnect the manometer and replace the screw and the
washer in the pressure outlet.
5.
Replace the control panel.
GB / IE - 2
5410.290.00