GLF10N /VMF-E4 CONNECTION
Connect the VMF-E4 to the GLF10N thermo-
stat; this connection must be made using a
4-pole shielded cable (maximum length 30
Characteristics of the cable to be used for the con-
nection:
• EIB Bus cable,
4 poles + shield;
• Mutual max capacity 100nF/km (800Hz);
• Resistance max 130 ohm/km;
Key:
A = 4-pole shielded cable (not supplied) for connection between
VMF-E4 and GLF10N ;
B = Shield folded on the cable for earth connection;
C = Clamp made of plastic conductive material (supplied) to be
fixed on the metallic structure of the fan coil;
D = Poles to be connected to the interface control board (sup-
plied) with the GLF10N card
28
AGLFI10NFJ 2006_5905226_03
meters); connect the terminals on the back
of the VMF-E4 to the supplied control board,
and complete the connection by inserting
1
2
1 2 3 4 5 6
1 2 3 4 5 6
the connector plug in the dedicated termi-
nal on the GLF10N card (as shown).
3 4