You must select "Partition" in the Operating Mode drop-down in LMCS in order to put the LMIN-104 into Partition Mode.
The LMIN-104 device allows a DLM system to automatically reconfigure the DLM devices in a space that has up to four movable walls.
Each combination of walls being Open or Closed is called a Profile in the DLM system; the LMIN-104 device transitions the system
from profile to profile as the walls get closed or opened. Commissioning of spaces containing movable walls is done using the standard
Push n' Learn concept used in regular spaces, the difference is that Push n'Learn needs to be repeated as many times as the number
of profiles expected. For example, if there is one wall, then Push n'Learn needs to be performed in the room 2 times (when the wall is
open and when the wall is closed - so there are 2 profiles being used).
Once all devices, including the LMIN-104, are installed, proceed with the following steps to configure the system for each of the profiles
expected. Note that if the LMPS-104 is also present in the same room, it will just act as a display device. The LED on the button
corresponding to the wall that has been closed will light up. The contact door as sensed by the LMIN-104 device has a higher priority
over button press.
1. Reconfigure the space for a specific profile by Opening or Closing the walls to represent one of the ways the space will be used
as. Note that the LEDs on the LMIN-104 will light up representing when a wall is closed, otherwise the corresponding LED will be
Off.
2. Enter into Push n' Learn mode from any device and configure the individual spaces so that the occupancy sensors and switches
get bound to the appropriate loads that belong to the same space. Refer to the LMSW-10x QSG and follow Step 1 for instructions
on how to enter Push n' Learn. Note also that only profile 1 (all walls open) will have default bindings that follow Plug n' Go rules,
all other profiles will have no bindings per default.
3. Exit Push n' Learn.
Follow the above steps for each additional profile.
Wiring in partition mode is identical to wiring a 2 wire maintained switch in Normal Mode. The four inputs correspond to the four walls. A
single 24VDC wire can be connected to all walls, or you may run separate 24VDC wires to each wall.
The LMIN-104 accommodates up to 4 movable walls representing a total of 16 different configurations (profiles). For each of these
profiles, there is a "Load Table" that contains the binding information between the switch/sensor and the load in the local IRB. The
following table lists the 16 different profiles. For additional details, see the Partition Examples on the next page.
PARTITION MODE
DLM local network
Wall 1
Wall 2
Wall 3
Wall 4
+24VDC
LOAD PROFILES
Partition Switch Cheat Sheet
4 Walls
3 Walls
2 Walls
1 Wall
0 Walls
DLM Profile # 1
2
3
4
Wall #1
0
1
0
1
Wall #2
0
0
1
1
Wall #3
0
0
0
0
Wall #4
0
0
0
0
0 = Open, 1 = Closed
With LMIN-104 and LMPS-104: Closed=LED On, Open=LED Off
WIRING
Blue LEDs
1
Connect to
LED 1
NOT Ethernet
2
LED 2
LED 3
3
LED 4
4
24V Overload
+24VDC
+24VDC
+24VDC
5
6
7
8
9 10 11 12 13 14 15 16
0
1
0
1
0
1
0
1
0
0
1
1
0
0
1
1
1
1
1
1
0
0
0
0
0
0
0
0
1
1
1
1
5
0
1
0
1
0
0
1
1
1
1
1
1
1
1
1
1