Installation shall be in accordance with all applicable regulations, wiring practices, and codes.
Connect to a Class 2 power source only.
• Class 2 Device Wiring Only – Do Not Reclassify and Install as Class 1, 3 or Power and Lighting
Wiring.
• Wire connections shall be rated suitable for the wire size (lead and building wiring) employed.
The LMIN-104 is UL2043 Plenum rated.
All connections to the LMIN-104 are Class 2 low voltage.
If code requires that the LMIN-104 be mounted in an enclosure, it can be mounted inside a 4" x 4"
junction box, inside a 21/8" deep (or deeper) 2-gang wall box, in a 3" or 4" octagonal box, or on a din
rail inside a panel.
Attach din rail clip
Attach the LMRJ Cable
The DLM local network uses free topology low voltage wiring. The LMIN-104 can connect anywhere on the DLM local network.
LMCS window for an LMIN-104 set to Normal mode.
MOUNTING AND WIRING
CAUTION: TO CONNECT A COMPUTER TO THE DLM LOCAL NETWORK USE THE LMCI-100.
NEVER CONNECT THE DLM LOCAL NETWORK TO AN ETHERNET PORT – IT MAY
DAMAGE COMPUTERS AND OTHER CONNECTED EQUIPMENT.
Option 1: Attach to din rail
Option 2: Mount to wall
Switch
LMRJ Cables
Occupancy Sensor
2
RJ45 ports (2)
Configuration LED
Configuration
push button
Switch Buttons
LEDs (5)
Input Wiring
Terminals
Inside a 2-gang J-box
Room
Controller
Input from Third Party Device
(example: BAS input, AV input)
Low Voltage Wires (1-4)
LMIN-104 Digital
Input Interface
Line Voltage
Loads
1
2