To Install The Outdoor Unit; To Provide Drainage; To Prevent The Outdoor Unit From Falling Over; Connecting The Refrigerant Piping - Daikin RXP20M5V1B Manual De Instalación

Ocultar thumbs Ver también para RXP20M5V1B:
Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 45
4 Installation
(mm)
In any case, provide at least 300  mm of free space below the unit.
Additionally, make sure the unit is positioned at least 100 mm above
the maximum expected level of snow. In this case, it is
recommended to construct a pedestal.
4.2.2

To install the outdoor unit

4.2.3

To provide drainage

NOTICE
If the unit is installed in a cold climate, take adequate
measures so that the evacuated condensate CANNOT
freeze.
INFORMATION
For information on the available options, contact your
dealer.
NOTICE
Provide at least 300  mm of free space below the unit.
Additionally, make sure the unit is positioned at least
100 mm above the expected level of snow.
1 Use a drain plug for drainage.
2 Use a Ø16 mm hose (field supply).
Installation manual
6
4× M8/M10
a
Drain port
b
Bottom frame
c
Drain plug
d
Hose (field supply)
4.2.4
To prevent the outdoor unit from falling
over
In case the unit is installed in places where strong wind can tilt the
unit, take following measure:
1 Prepare 2 cables as indicated in the following illustration (field
supply).
2 Place the 2 cables over the outdoor unit.
3 Insert a rubber sheet between the cables and the outdoor unit
to prevent the cables from scratching the paint (field supply).
4 Attach the ends of the cables and tighten them.
4.3

Connecting the refrigerant piping

DANGER: RISK OF BURNING
4.3.1

About connecting the refrigerant piping

Before connecting the refrigerant piping
Make sure the outdoor and indoor unit are mounted.
Typical workflow
Connecting the refrigerant piping involves:
▪ Connecting the refrigerant piping to the indoor unit
▪ Connecting the refrigerant piping to the outdoor unit
▪ Insulating the refrigerant piping
▪ Keeping in mind the guidelines for:
▪ Pipe bending
▪ Flaring pipe ends
▪ Using the stop valves
b
a
c
d
(A)RXP20~35M5V1B
R32 split series
3P519299-5B – 2018.12
Tabla de contenido
loading

Este manual también es adecuado para:

Rxp25m5v1bRxp35m5v1bArxp20m5v1bArxp25m5v1bArxp35m5v1b

Tabla de contenido