Technical Data - ABB Powernet EIB 6972 AG-102-500 Instrucciones De Uso

Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 82

Technical Data

Power supply:
Nominal voltage:
Current consumption:
Switching current:
Shutter acutator mode:
Series actuator mode:
Pushbuttons:
Max. line length:
No. of pushbuttons (unlit):
Pushbutton input:
Connections (see Fig. 1):
- ABB Powernet EIB:
- Pushbutton input:
- System input:
- System overcoupling:
- Switching outputs:
- Terminal load:
General:
Operating temperature:
Storage and transport:
Type of protection:
Dimensions (h x w x d):
Weight:
230 V ~ ± 10 % , 50 Hz
≤ 20 mA
max. 5 A, cos ϕ = 0.5
max. 2 x 10 A, cos ϕ = 0.5 (in polyphase operation)
max. 10 A, cos ϕ = 0.5 (in single-phase operation)
100 m per pushbutton input
unlimited
230 V ~ ± 10 % , 50 Hz
phase selection by means of a 7-pole plug-in terminal
3-pole screw/plug-in terminal
5-pole screw/plug-in terminal
5-pole screw/plug-in terminal
2 x 4-pole screw/plug-in terminal
phase selection by means of a 7-pole plug-in terminal
max. 10 A for all N and L terminals
- 5 to + 45 °C
- 20 to + 70 °C
IP 54 acc. to EN 60529
105 x 150 x 50 mm
0.4 kg
GB