Remote Control Adjustments-Installer - S&P IDEO 450 ECOWATT Manual Del Usuario

Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 1
5. REMOTE CONTROL ADJUSTMENTS – INSTALLER
The remote control allows:
-
Adjust the airflows (1
-
Timer for adjusting the filter maintenance period (6, 9, 12 or 15 months) (factory
setting 9 months)
-
Adjust the balance of supply / extraction airflows
Adjustment of the airflows
st
(1
) Low speed
adjustment
To adjust the airflow turn the potentiometer carefully clock wise with a small screw driver.
There are 16 positions 0-1-2-3-4-5-6-7-8-9-A-B-C-D-E-F. Position 0 = 0V and position
A=10V. The positions from B to F are all 10V. We do not recommend to set the
potentiometer speed lower than position 4=4V.
st
Factory setting: 1
speed = 4; 2
Adjustment of the filter maintenance period
It is possible to set the period to 6, 9, 12 or 15 months (9 months factory setting). The filter
clogging depends on the pollution of the area where the unit is installed. We recommend
checking the time in which the filter clogs and adjusting this period. It is advisable to do this
after the second filter change. Of course, after the installation, the extract air is dusty and not
representative. During the second filter check, if you notice that the filters are clean you can
increase the time (12 or 15, months), if you notice that the filters are very dirty you should
decrease the time (6 months).
Open the box and adjust the timing as shown. To do this, set the micro contacts 1 and 2 as
shown in the drawings below to adjust the month.
Filters alarm timing
6 months
st
nd
speed, 2
speed, 3
nd
speed = 6 and 3
9 months
(factory setting)
31
rd
speed)
rd
speed = 10.
12 months
rd
(3
) High speed
adjustment
nd
(2
) Middle speed
adjustment
15 months
Tabla de contenido
loading

Tabla de contenido