ABB RS 485 Serie Manual De Operación
ABB RS 485 Serie Manual De Operación

ABB RS 485 Serie Manual De Operación

Interface unión serie fibra óptica

Enlaces rápidos

233121
041001
ILPH Optical Fiber
1
2
3
4
5
RS485 / FO
Version 3.0
07.03
M L K
J H G
D E F
A B C
Serial link interface
RS 485 / Optical Fiber
Operating manual
The device must be installed by a qualified engineer.
Set-up and configuration:
1
LED „U"
Power supply status
2
Optical Fiber emitter
ST connector for glass fiber
FSMA screw connector for plastic fiber
3
LED „TD"
Data transmission status
4
Optical Fiber receiver
ST connector for glass fiber
FSMA screw connector for plastic fiber
5
LED „RD"
Data reception status
Connections:
1 RS 485 2-wires: IEC 8482 / DIN 66 259-4 EIA 485
Connections:
Input/Output data
Input/Output data
Signal ground
Shield
Technical data:
Standard:
Transmission speed :
Transmission distance: max. 1200m
2 Optical Fiber
Connections:
Optical fiber emitter
Optical fiber receiver
Technical data:
Fiber type:
Connections:
Glass:
Plastic:
Wave length:
Glass:
Plastic:
Max transmission power:
Glass 50/125 µm:
Glass 62,5/125 µm:
Plastic 980/1000 µm:
Reception sensitivity min.:
Glass 50/125 µm:
Plastic 980/1000 µm:
Maximum transmission distance:
Glass 50/125 µm:
Glass 62,5/125 µm:
Plastic 980/1000 µm:
3 Power supply
Connections:
Power supply voltage
Power supply voltage
Protective earth
Shielding terminals
Operating voltage:
See the label on the product
Voltage
24.. 42VAC/DC
110..240VAC/DC
English
D+
(B)
- terminal M
D-
- terminal L
(A)
0V
- terminal K
SH
- terminal G
RS 485 2-wires half duplex
max. 1,5Mbits/s
Multimode fiber
ST connector
FSMA screw connector
820nm
655nm
-14,4dB/m
-14 dB/m
- 8 dB/m
-28 dB/m
-20 dB/m
3km
4km
40m
~/+
- terminal B
~/-
- terminal C
- terminal A
- terminals D, E, F
Tolerance
Frequency
-15%..+10%
50/60Hz
-15%..+10%
50/60Hz
loading

Resumen de contenidos para ABB RS 485 Serie

  • Página 1 Version 3.0 07.03 233121 041001 ILPH Optical Fiber Serial link interface English RS 485 / Optical Fiber M L K Operating manual The device must be installed by a qualified engineer. Set-up and configuration: LED „U“ Power supply status Optical Fiber emitter ST connector for glass fiber J H G FSMA screw connector for plastic fiber...
  • Página 2 Version 3.0 07.03 233121b 030731 English Connection hints Table 1 RS 485 The RS 485 interface has been designed for a 2 wire connection and half duplex use. With the SW1.2 and 1.3 dip-switches the steady state can be configured through polarization resistors.
  • Página 3 Version 3.0 07.03 233121 041001 Interface de liaison série Schnittstellenumsetzer Français Deutsch RS 485 / Fibre optique RS 485 / Lichtwellenleiter Bedienungsanleitung Notice d’utilisation Nur von einer Fachkraft zu installieren. L’installation de ces produits doit être réalisée par une personne Bedien- und Einstellinstrumente: compétante.
  • Página 4 Version 3.0 07.03 233121b 030731 Deutsch Français Précaution de raccordement Anschlusshinweise RS 485 RS 485 Die RS 485 ist als 2 Draht Schnittstelle für das Halbduplex- La liaison RS 485 est conçue pour une connexion 2 fils et verfahren ausgelegt. Mit den Schaltern SW1.2 und 1.3 kann une utilisation half duplex.
  • Página 5 Version 3.0 07.03 233121 041001 Interface unión serie Español Interfaccia di trasmissione Italiano RS 485 / Fibra óptica seriale RS 485 / Fibra ottica Manuale Operativo Manual de operación Il sensore puó essere installato esclusivamente da un tecnico La instalación de éstos aparatos debe ser realizada por alguien specializzato.
  • Página 6: Tipo De Conexiones

    Version 3.0 07.03 233121b 030731 Español Italiano Tipo de conexiones: Suggerimenti sulle connessioni: RS 485 RS 232 El interface RS 485 ha sido diseñado para la unión de dos hilos L’ interfaccia RS 485 è stata progettata per una connessione con una utilización half duplex .Mediante los interruptores tipo a 2 fili ed uso half duplex.