Configuration of the control panel
7.1. Configuration of delays.
The delays of the "Sounder relay output" and "Fault relay output" are configured using the
control keys on the control panel.
The time indication for these delays is displayed in binary
code using the Battery Fault indicator, CPU Fault, COM
and Keyboard Access leds.
Note:
the
programmed
independently of the alarm comes from a detector, a
manual call point, or a combination of them.
Figure 8: led indicators used for delay time configuration.
The procedure is as follows:
1) Activate access level 2 (press the control keys once in the following order: Zone/Relay
selection, Reset/Autotest, Zone/Relay selection, Reset/Autotest).
2) Activate access level 3 (press the control keys once in the following order: Test mode,
Disable, Test mode, Disable).
3) Select the relay to which you wish to apply the delay using the control key Select
Relay.
4) Press the control key No delay in order to select the times. These are shown in the
following table along with the corresponding state of the indicator lamps:
Note: The first button indicates the current delay.
Nº Pulsaciones
1
COM
Sounder Relay
0
(minutes)
Fault Relay
0
(minutes)
R2 Relay
0
(seconds)
Unlocking
Delay
0
(minutes)
Figure 9: Correlation between the N
44
Ctra. de Molins de Rei a Rubí, Km. 8,4 - 08191 RUBÍ (Barcelona) ESPAÑA.
Conventional Fire Detection and Fire Alarm Control Panel
CLVR02EXT
delays
are
maintained
2
3
4
5
1
2
3
4
1
2
3
4
5
10
15
20
5
10
15
20
er
of pressings of the no delay control key, the state of the indication
leds and the configured delay times.