Indicator leds are described hereafter:
KEY
ALARM
Red
Power Supply
Bateria / Battery
Avería General
General Fault
Av. Alimentación
Supply Fault
Relé Sirena
Sounder Relay
Relé Avería
Fault Relay
Avería Batería
Battery Fault
Avería CPU
CPU Fault
COM
Acceso Teclado
Keyboard Access
L
sin Retardo
M
no delay
desconexión
N
general disable
modo pruebas
O
test mode
ALARM
AVERÍA / FAULT
PRUEBA / ANULADO
TEST / DISABLED
R1
R2
DISPARO RELÉ
S
RELAY TRIGGER
AVERÍA / ANULADO
T
FAULT / DISABLED
BLOQUEO RELÉ
U
RELAY LOCKED
Ctra. de Molins de Rei a Rubí, Km. 8,4 - 08191 RUBÍ (Barcelona) ESPAÑA.
Conventional Fire Detection and Fire Alarm Control Panel
CLVR02EXT
LED
COLOUR
Fire alarm due to activation of manual call point or detector.
A
Red
► Fixed
System operating through 230 V/AC power supply.
B
Green
► Fixed
System operating under batteries.
C
Green
► Fixed
System fault
D
Amber
► Fixed
General power supply fault.
E
► Fixed Fault 230V/AC input, batteries input, 30V output, etc
Amber
General sounder output condition
F
► Fixed Relay triggered
Amber
► Intermittent Fault in the relay, line open, line crossed, sounder fuse
etc.
Condition of fault output
G
► Fixed Relay triggered
Amber
► Intermittent Fault in relay, line open, line crossed, fuse fault etc.
Fault in the auxiliary battery supply
H
► fixed Batteries faulty, discharged or missing.
Amber
► Intermittent Fault in the battery charger.
CPU fault
Amber
I
► Fixed Control Panel not operating.
Control Panel communication through RS485 port
J
► Intermittent Control panel communicatin
Amber
Level of access to keyboard of Control Panel.
► Off Level 1.
K
Amber
► Fixed Level 2.
► Intermittent Level 3.
Silence sounders
► Fixed General relay sounder in silent position.
Amber
Disable delays of panel
► Fixed Control panel operating without delays at the general sounder
Amber
outputs, fault and extinguishing relay "R2".
Zone out of service.
► Fixed At least 1 zone out of service.
Amber
Zone in test mode
► Fixed At least 1 zone in test mode.
Amber
Alarm in zone indicated.
1
► Fixed activated by manual call point
Red
P
► Intermittent activated by Detector
Fault in zone indicated.
► Fixed Open line fault.
Amber
Q
► Intermittent Crossed line fault.
Zone indicated in test or disabled
► Fixed Zone disabled.
R
Amber
► Intermittent Zone in test.
Condition of relay.
► Fixed Relay triggered.
Amber
► Intermittent Relay activated in countdown (only extinguishing relay
R2).
Relay fault or disabled.
► Fixed Relay disabled.
Amber
► Intermittent Relay fault (Relay fault, line open, line crossed, etc).
Extinguishing relay locked (R2).
► Fixed Activated Emergency abort. Panel may be reset.
Amber
► Intermittent
countdown.
FIRE PROTECTION MANUFACTURER
DESCRIPTION
Extinguishing triggered. Delay time for reset still
33